WARNING
When activating C014, the mechanical rotation of the connected motor and its load is
reversed accordingly.
C015
Rated Motor Frequency
Range
10
10000
1.0 Hz
1000.0 Hz (See upper limits in Table 11)
Default
500
Level
BASIC
Address
1015
Function
This parameter defines the rated motor frequency (nameplate rating).
Table 11: Maximum value of the output frequency depending on the drive size
Size
Max. output frequency
(Hz)
(*)
2T/4T
Smaller than 0015
1000
0015 to 0129 (**)
625
0150 to 0162
500
Greater than 0162
400
(**)
From 0023 to 0030 (437.5Hz), 0040 (1000Hz) and 0049 (800Hz)
Size
Max. output frequency
(*)
5T/6T
Smaller than 0076
500
0076 to 0524
400
Greater than 0524
200
(*) NOTE
The maximum output frequency is limited to the speed level programmed in parameters C028,
C029 [
–32000 ÷ 32000]rpm. This results in Fout
max
= (RPM
max
*NPole)/120.
C016
Rated Motor RPM
Range
1
32000
1
32000 rpm
Default
1420
Level
BASIC
Address
1016
Function
This parameter defines the rated motor rpm (nameplate rating).
C017
Rated Motor Power
Range
1
32000
0.1
3200.0 kW (Upper limited to twice the default value)
Default
Depending on the size
Level
BASIC
Address
1017
Function
This parameter defines the rated motor power (nameplate rating).