^SynOhrMultiSenseKNX-Eng-13.odt, 2014-05-06 Page 19 of 49
Picture 16: Setpoints in the ETS
•
Different operating modes can be activated for the room controller: comfort, standby,
night- and building protection.
•
Each operating mode can be its own temperature setpoints (for heating and/or cooling)
assigned.
•
Parameterizable duration of comfort prolongation.
•
Changing of the operating modes by 1byte object to KONNEX or by up to 4 individual 1
bit objects.
•
Frost-/heat protection switching by window status.
•
Display of the room temperature controller information on the device display.
•
Modes „Heating“, „Cooling“, „Heating and Cooling“ with or without auxiliary step.
•
For each heating or cooling stage are different types of control configurable. PI-control
(continuous or switching PWM) or 2-point control (switching).
•
Control parameters for PI-controller (if desired: proportional band, reset time) and 2-
point controller (hysteresis) is adjustable.
•
The temperature setpoints for the additional stage are derived via a configurable level
distance from the values of the basic level.
•
Automatic or object oriented switch-over between „Heating“ and „Cooling“.
•
Setpoint shift temporarily or permanently possible by operating the function keys on the
device or via communication objects (e.g. by a controller extension).
•
Complete (1 byte) or partial(1 bit) status information about objects parameterized and
transmitted to the bus.
•
Deactivation of the control or of the additional stage via separate 1 bit objects possible.
•
Internal and external temperature sensor for room temperature measurement is
possible.
•
The room temperature measurement (actual value) can be adjusted via parameter
separately for internal and external sensor.
•
The actual and desired temperatures can be issued after a configurable deviation on the
bus (also cyclic).
•
Separate or joint alternate size output in heating and cooling mode. Thereby one or two
variables objects per level.
•
Normal or inverted alternate size output configurable.
•
Automatic transmission and cycle time for alternate size output configurable (Note: the
parameter „Cyclical Turn (min)“ is only relevant if a PI-controller is configured with
switching alternate size).
Enertex
®
Bayern GmbH – Ebermannstädter Straße 8 - 91301 Forchheim - [email protected]