22
Bentone
5.7 Replacing individual electrical
package components
1.
Switch off mains power and disconnect the Europlug from the burner.
2.
Remove the burner from the boiler by loosening the screw (A).
3.
Remove the burner control and loosen the two bottom screws in the
relay socket.
4.
The Europlug plate is firmly attached under the relay socket.
5.
Remove the cable of the component to be replaced.
6.
Connect the new cable.
7.
Refit the electrical package (do not forget the Europlug).
8.
Turn on the burner control.
9.
Connect the Europlug and turn on the mains power.
10. Start the burner and check the combustion.