Handling

DataSafe

®

 HX batteries are supplied in a charged 

condition and are capable of extremely high short 

circuit currents. Take care to avoid short-circuiting 

terminals of opposite polarity.

Important

Please read this manual immediately on receipt of the battery before unpacking and installing. Failure to comply with these instructions will render any warranties 

null and void.

Care for your safety

2

     

AM-12HX1000F-IOM AA September 2020

   

Keep flames away

In case of accidental overcharge a flammable gas 

can leak off the safety vent.

Discharge any possible static electricity from clothes 

by touching an earth connected part.

Tools

Use tools with insulated handles.

Do not place or drop metal objects on the battery.

Remove rings, wristwatch and articles of clothing with metal 

parts that may come into contact with the battery terminals.

No smoking, 

no naked flames, 

no sparks

Read 

instructions

Electrical 

hazard

Danger

Recycle scrap 

batteries. 

Contains lead

Electrolyte is 

corrosive

Clean all acid splash in eyes or on skin 

with plenty of clean water. Then seek 

medical help. Acid on clothing is to be 

washed with water

Warning: Risk of fire, explosion, or burns. Do not 

disassemble, heat above 60°C (140°F), or incinerate. 

Avoid any short circuit. Metallic parts under voltage on the 

battery, do not place tools or items on top of the battery

California Proposition 65 Warning

 - Battery posts, terminals, and related accessories contain lead and lead compounds, chemicals known to the State of California to 

cause cancer and reproductive harm. Wash hands after handling.

DANGER

 

Contains: Lead, Sulfuric Acid (Electrolyte), Lead Compounds.
Harmful if swallowed, inhaled, or in contact with skin. Acid causes severe skin burns 

and eye damage. May damage fertility or the unborn child if ingested or inhaled. 

May cause harm to breast-fed children. May cause cancer if ingested or inhaled. 

Causes skin irritation, serious eye damage. Contact with internal components may 

cause irritation or severe burns. Causes damage to central nervous system, blood 

and kidneys through prolonged or repeated exposure if ingested or inhaled. Irritating 

to eyes, respiratory system, and skin. May form explosive air/gas mixture during 

charging. Extremely flammable gas (hydrogen). Explosive, fire, blast or projection 

hazard.
Obtain special instructions before use. Do not handle until all safety precautions 

have been read and understood. Wash thoroughly after handling. Do not eat, drink 

or smoke when using this product. Avoid contact during pregnancy/while nursing. 

Wear protective gloves/protective clothing, eye protection/face protection. Use 

only outdoors or in a well-ventilated area. Avoid contact with internal acid. Do not 

breathe dust/fume/gas/mist/vapors/spray. Keep away from heat/sparks/open flames/

hot surfaces. No smoking. IF SWALLOWED OR CONSUMED: rinse mouth. Do NOT 

induce vomiting. Call a poison center/doctor if you feel unwell. IF ON CLOTHING 

OR SKIN (or hair): Remove/Take off immediately all contaminated clothing and wash 

it before reuse. Rinse skin with water/shower. IF INHALED: Remove person to 

fresh air and keep comfortable for breathing. Immediately call a POISON CENTER 

or doctor/physician. IF IN EYES: Rinse cautiously with water for several minutes. 

Remove contact lenses, if present and easy to do. Continue rinsing. If exposed/

concerned, or if you feel unwell seek medical attention/advice. Store locked up, 

in a well-ventilated area, in accordance with local and national regulation. Dispose 

of contents/container in accordance with local and national regulation. Keep out of 

reach of children.

1. Receiving the Shipment

Carefully examine the battery shipment upon arrival for any signs of transit 

damage and that it agrees with the materials list or packing slip. Be very careful 

not to inadvertently discard any accessories contained in the packing material.
Batteries contain sulfuric acid in glass fiber separators.
Use rubber gloves when handling broken or damaged containers in case of 

acid leakage.

2. Storage

Store 

DataSafe

®

 12HX-FT

 batteries in a dry, clean and preferably cool location.

Since the batteries are supplied charged, storage time is limited. In order to 

easily charge the batteries after prolonged storage, it is advised not to store it 

more than:

  6 months at ambient temperature no warmer than 77°F (25°C)

  4 months at 86°F (30°C)

  2 months at 104°F (40°C)

Give the battery a freshening charge before the end of the recommended 

storage interval.
A refreshing charge shall be performed at 2.27 volts per Cell (Vpc) at 77°F 

(25°C) or 13.62 Volts per Battery (volts per block) for 96 hours or until the charge 

current does not vary for a three hour period.
The necessity of a charge can also be determined by measuring the open 

circuit voltage of a stored battery.
Charging is advised if the voltage drops below 2.07 Vpc. or 12.42 volts per 

block
Maximum total storage prior to installation is two years from date of shipment 

from the factory to the customer when stored at 77°F (25°C). Freshening 

charges are required before the end of the storage time period or more 

frequently, as noted above.

Failure to observe these conditions may result in greatly reduced capacity and 

service life.

FAILURE TO CHARGE AS NOTED VOIDS THE BATTERY’S WARRANTY.

3. Installation

Install in clean, dry area. DataSafe 12HX-FT batteries release minimal amounts 

of gas during normal operation (gas recombination efficiency 

 97%). The 

batteries can be installed near the main equipment. Batteries must be 

installed in accordance with federal, state and local law regulations and the 

manufacturer’s instructions.

  Temperature

Avoid placing batteries in areas of high temperature or in direct sunlight. The 

batteries will give their optimum service life when operating at a temperature 

between 68°F (20°C) and 77°F (25°C), however they are capable of operating 

in a temperature range of -22°F (-30°C) to 122°F (50°C). Please reference the 

charging float voltage section for more information regarding float voltage 

adjustments for temperature variations. Reasonable precautions should be 

taken to prevent continuous operation below -22°F (-30°C) or above 122°F 

(50°C).

  Ventilation

Under normal conditions gas release is very low and natural ventilation is 

sufficient for cooling purposes and inadvertent overcharge, enabling DataSafe 

12HX-FT batteries to be used safely in offices and with main equipment.
However, care must be taken to ensure adequate ventilation when placed in 

cabinets. Batteries must not be placed in sealed cabinets.

  Stowing

For proper installation, EnerSys

®

 battery racks and cabinets are recommended.

Attention: Unless otherwise noted, battery racks and cabinets should not be 

transported with rigid intercell connectors in place.
Intercell connector covers should be installed after completing the intercell 

connections.

BCI Warning

Shield 

eyes

Pb

Reviews: