0170022-J0 Rev A
Page 12
4.2
Feature Description
Table 5:
Feature Description (Sheet 1 of 2)
Feature
Description
AC Input Circuit Breaker
This circuit breaker is an On/Off switch for the utility/line power into the
unit. It must be switched On for proper operation.
Battery breaker
This circuit breaker provides over-current protection and is used as an
On/Off switch for the battery power. It must be switched On for proper
operation.
Battery connector
The battery connector connects the external batteries to the unit.
Battery temperature
sensor connector
The battery charging voltage is temperature dependent when
compensation is not set to 0 mV/°C/cell. A battery temperature sensor
connects to the unit so the microprocessor can adjust the charging
voltage for optimum charging. Refer to
UPS Maintenance > Battery
.
The sensor MUST be attached to the unit for normal operation. If the
sensor is not attached, a “Temperature Probe Unplugged” alarm
appears on the LCD.
Battery voltage test points
These test points accept 2mm diameter test probe tips. The battery
circuit breaker must be on to measure the battery voltage.
NOTE
:
The battery voltage test points are not to be used as a power port.
CAN connection
CAN connector connects additional Input/Output ADIO modules to the
system.
Ethernet (1 & 2)
Ethernet ports 1 and 2 connect the unit system to the network.The
default IP address for Ethernet Port 1 is 192.168.0.90 and the Ethernet
Port 2 is Auto.
Fan assembly
This microprocessor-controlled fan turns on at a preset temperature to
lower the unit’s internal temperature. It must not be blocked. An Alarm
is generated if the fan fails; a failed fan can be replaced in the field.
Input Terminal Block
The unit’s AC line power input.
LCD control panel
The LCD control panel is used to monitor and control the unit.
LED
Green LED solidly illuminated: the unit is in Line mode and line power
is provided to the load.
Green LED flashing: the unit is in Inverter mode and backup battery
power is provided to the load.
Yellow LED solidly illuminated: there is one or more minor active alarm
in the unit.
Red LED solidly illuminated: there is one or more major or critical
active alarm in the unit.
Summary of Contents for Alpha FXM HP 1100
Page 1: ...Alpha FXM HP 650 1100 2000 UPS Technical Guide 0170022 J0 Effective 11 2019...
Page 2: ......
Page 4: ......
Page 12: ...viii...
Page 28: ...0170022 J0 Rev A Page 16...
Page 30: ...0170022 J0 Rev A Page 18...
Page 142: ...0170022 J0 Rev A Page 130 Figure 70 Upgrade Succeeded...
Page 144: ...0170022 J0 Rev A Page 132...
Page 146: ...0170022 J0 Rev A Page 134...
Page 148: ......
Page 149: ......