EnerPro VR31 Operation Manual Download Page 3

 

Enerpro Document No: OP-0116; Rev.

 

A

 

Page 3 of 3

ECO #19-11073; Release Date: 07/23/2019 

 

5. 

Output Out of Range.  

Voltage outside the ranges listed above may be due to VR31 

malfunction, a defective AuxGen (Step 1) or a defective or damaged battery. Note that the output 
measured is rectifier voltage, not battery voltage. Because of diode drop and cabling resistance, 
battery voltage may be as much as 6 volts lower than rectifier voltage depending on battery state 
of charge and health. 
 

a. 

Stage 1 voltage low.

 With the Stage 1 LED illuminated, check battery current IB. If IB is 

normal (0.8- 0.95 VDC, 80-95 amps), check RP voltage. If RP voltage is 68 VDC or 
above, allow to run and check again in 1 hour. If RP is below 68 VDC or does not 
increase after 1 hour, test battery for shorted cells or other defects. 

b. 

Stage 1 battery current out of range.

 If Stage 1 is illuminated and IB is out of range 

(0.8- 0.95 VDC, 80-95 amps), remove and replace VR31. 

c. 

Stage 2 or 3 voltage out of range.

 Remove and replace VR31. 

 