Enerlites MWOS Installation Instructions Download Page 2

4

5

6

WARRANTY INFORMATION

TROUBLESHOOTING

OPERATION

This device is warranted to be free of material and workmanship defects for 2 years from the 

date of purchase. Original receipt or proof of purchase from an authorized retailer must be 

presented upon warranty claim. ALL claims must be verified and approved by Enerlites, Inc. 

Warranties from other Enerlites products may vary. This warranty is nontransferable and does 

not cover normal wear and tear or any malfunction, failure, or defect resulting from misuse, 

abuse, neglect, alteration, modification, or improper installation.  To the fullest extent 

permitted by the applicable state law, Enerlites shall not be liable to the purchaser or end user 

customer of Enerlites products for direct, indirect, incidental, or consequential damages even 

if Enerlites has been advised of the possibility of such damages.  Enerlites’ total liability under 

this or any other warranty, express or implied, is limited to repair, replacement or refund.  

Repair, replacement or refund are the sole and exclusive remedies for breach of warranty or 

any other legal theory.

©

 

2016 Enerlites Inc.

 

CA, U.S.A.

020

7

1600

30

The 

OFF

 position:

 Switch is turned off and will not detect motion. The 

push button will not function.

OCC

upancy position:

 The load will automatically turn on when motion is 

detected and automatically turn off when the selected time delay has 

expired.

 The push button may be used to manually turn ON/OFF the load 

and time delay will also take effect.

VAC

ancy position:

 The load will turn on ONLY when the push button is 

used and automatically turn off when the selected time delay has expired. 

The push button may be used to manually turn ON/OFF the load and time 

delay will also take effect. If the time delay has expired and the load turns off, 

the load will turn on again automatically if motion is detected within 30 

seconds.

1.

Push Manual On/Off Button, if the load turns On; verify that 

the

 

Ultrasonic

dial 

is on high

 and/ or the PIR switch is set to 100%

.

2.

Check the wiring connections

. Be sure the

 N

EUTRAL

 wir

e is present

.

3.

Switch may be in VACancy mode. Select the OCC position on the Mode 

Switch if "Auto ON" is what's desired.

NOTE: There is a 1 minute warm-up time at initial power-up. The load 

may turn on/off several times.

The Load does not turn On. LED does not flash regardless of motion:

The Load does not turn On

 when LED indicator flashes and motion is 

detected

:

1.

Push Manual On/Off Button, if the load turns On; 

verify that the Ultrasonic 

dial is on high and/ or the PIR switch is set to 100%.

2.

Check the wiring connections

. Be sure the

 

LOAD

 wir

e is connected

.

3.

Switch may be in VACancy mode. Select the OCC position on the Mode 

Switch if "Auto ON" is what's desired.

4.

Check the 

Light

 dial. The pointer indicates the light level the ambient light 

needs to drop to before the load is automatically turned on.

The Load does not turn Off:

The Load turns on when its not desired:

1.

Motion may be detected. The time delay constantly restarts its countdown 

after the last motion detected. To verify proper operation, 

set

 the Time 

Delay 

switches

 to 15s (Test Mode) and make sure there is no motion (no 

LED flashing). Tape may be used to cover the fresnel lens 

and ultrasonic 

cones 

while testing.

2.

Check for significant heat source emitting within six feet (two meters) such 

as high wattage light bulb, portable heaters or HAVC vents.

3.

If Manual operation of push-button is desired, select VAC mode on the 

Mode Switch.

4.

If the sensor is installed in a small room, turn the Range dial lower

 to avoid 

false or unwanted detection from open window or door.

 

1.

Motion may be detected. The time delay constantly restarts its 

countdown after the last motion detected.

2.

To verify proper operation, turn the Time Delay Knob to 15s (Test 

Mode) and make sure there is no motion (no LED flashing). Tape may 

be used to cover the fresnel lens while testing.

3.

Check for significant heat source emitting within six feet (two meters) 

such as high wattage light bulb, portable heaters or HAVC vents.Check 

the wiring. Make sure the HOT and LOAD wires aren't reversed. 

DIP SWITCH SETTINGS

5 Minutes

Walk Through

PIR Sensitivity

50%

100%

Disabled

Enabled

Time Delay

15 Sec/Test

10 Minutes

15 Minutes

20 Minutes

25 Minutes
30 Minutes

1

7

4 5 6

The MWOS has 7 DIP switches under the cover. They are used to 

set 

sensitivity, time 

delay, trigger mode, walk through mode feature 

settings.

PIR Sensitivity setting: Switch 1

50%

, sensor's coverage 

about 600 square feet

100%

,

 

  the maximum range of 

sensor's PIR coverage is 1200 square feet, see "coverage pattern".

Trigger Mode: Switches 2, 3

The sensor has 4 trigger options

. Use DIP switches 2 & 3 and follow t

he 

chart 

above for "Trigger Mode": 

Both:

 requires motion detection by the PIR and the Ultrasonic.

Either: 

requires motion detection by only one technology (whichever 

detects motion first).

PIR:

 requires motion detection only by the PIR.

US:

  requires motion detection only by the Ultrasonic. 

1 Minute

Trigger Mode Initial 

Trigger Load Output

Maintain

Re-trigger

2

3

Both

Either

Either

PIR

PIR

PIR

Both

Both

Both

US

Option 1
Option 2
Option 3
Option 4

US

US

Time Delay: Switches 4, 5, 6
The sensor will hold the lights on as long as occupancy is detected

 based on the 

trigger mode selected

. The 

time delay countdown starts when no motion is 

detected

 and 

the sensor will turn the lights off

 when the time expires

.

Walk-through mode: Switch 7

I

f no motion is detected 

within

 the first 30 seconds

 

after the initial detection, 

the 

sensor will turn the lights off 

in 

three minutes

. If motion continues beyond the 

first 30 seconds, the selected time delay applies.

=Factory Setting

=OFF     =ON      

OCC  

Mod

e

OFF

VAC 

Description

Position

Left

Center

Right

Circuit is permanently opened.

(switched off)

Occupancy Mode:

Automatic On, Automatic Off 

after 

selected

 time delay. 

Vacancy Mode: Manual On 

only, Automatic Off after 

selected

 time delay.

Push-

B

utton 

Function

Manually toggles 

None

Manually toggles 
On / Off the load.

On/Off the load.

Off/ Occupancy/

Vacancy Mode Switch

OFF   OCC   VAC

Push Button