(Hot)
(Load)
(Neutral)
Black
Red
White
Grey1
Grey2
Wiring Directions
WARNING: Turn off the power at the circuit breaker before installing
Refer to the wire diagram of the sensor (see figure 2), and connect the wires of
ceiling sensors as followed by using the wire nuts provided. 1. Connect the Hot wire
of main power to the Black wire from the sensor. 2. Connect the Load wire to the
Red wire from the sensor. 3. Connect the Neutral wire of Load and main power to the
White wire from the sensor. 4. Connect the two Grey wires( 22AWG) to the terminals
of the momentary switch. You can add a MANUAL SWITCH such as the Momentary
Switch to the sensor by connecting the Grey wires.
(Step 4 is not necessary if you don't want to use the function of MANUAL ON/OFF )
Figure 2
mounting
Mounting
Using an Octagonal Junction Box
1. Pull the high voltage wires into the J-Box through the conduit knockout.
2. Connect the high voltage wires to the appropriate terminals on the sensor.
3. Loosen the appliance mounting screws attached to the J-Box.
4. Align the sensor in the J-Box so that the mounting screws on the box match
the key holes on the sensor's rear housing.
5. Push the sensor up into the J-Box and twist it so that the mounting screws
are seated in the keyhole slots.
6. Tighten the two screws to secure the sensor to the J-Box.
7. Snap the front cover onto the sensor(see Figure 3)
Front Cover
Rear Housing
Wire
Screws
Octagonal box
Drop Ceiling
Figure 3