ENERGY CONSERVATORY Flow Meter Operation Manual Download Page 15

Appendix B

     Calibration and Measurement Accuracy

8

The

 

ENERGY

CONSERVATORY

DIAGNOSTIC TOOLS TO MEASURE BUILDING PERFORMANCE

Appendix B     Calibration and Measurement Accuracy

B.1  Exhaust Fan Flow Metering Box Calibration Formula

Door Opening

Formula 

E1

Flow (CFM) =  43.73  x  (Metering Box Pressure in Pascals)

0.5

E2

Flow (CFM) =  20.72  x  (Metering Box Pressure in Pascals)

0.5

E3

Flow (CFM) =  10.07  x  (Metering Box Pressure in Pascals)

0.5

B.2  Specifications

Flow Accuracy:

+/- 10% when used with a 1% pressure gauge (DG-700, DG-3 or DG-2). 

Flow Range: *

System Weight:

4 lbs. including the extension pole.

Dimensions:

Inside opening (13” x 16” x 8” deep).

* The upper flow range limit of 124 CFM is based on the assumption that back pressures greater than    
8.0 Pascals will start to restrict air flow through typical residential exhaust fans. The Metering Box will accurately
measure flows above 124 CFM, however the measured flow may be less than the actual flow through the exhaust
fan under normal operating conditions. Referring to the manufacturer's published fan curve for the exhaust fan being
tested will allow you to estimate how much the back pressure added by the Metering Box has reduced the air flow
through the exhaust fan. 

Door Position

Flow Range (CFM)

E1

44 -124

E2

21 - 59

E3

10 - 28

Summary of Contents for Flow Meter

Page 1: ...Exhaust Fan Flow Meter Operation Manual The ENERGY CONSERVATORY DIAGNOSTIC TOOLS TO MEASURE BUILDING PERFORMANCE...

Page 2: ......

Page 3: ...nual The Energy Conservatory 2801 21st Ave S Suite 160 Minneapolis MN 55407 612 827 1117 Fax 612 827 1051 www energyconservatory com email info energyconservatory com Exhaust Fan Flow Meter is a trade...

Page 4: ......

Page 5: ...n lieu of all other warranties and is subject to the conditions and limitations stated herein No other express or implied warranty IS PROVIDED AND THE SELLER DISCLAIMS ANY IMPLIED WARRANTY OF FITNESS...

Page 6: ......

Page 7: ...a Pressure Gauge 2 2 2 Select the Door Position on the Metering Box 3 2 3 Attach the Handle to the Metering Box 3 2 4 Turn On and Configure the Pressure Gauge 4 2 5 Place Metering Box Over Exhaust Fan...

Page 8: ...y over the exhaust fan grille and is pushed up against the wall or ceiling so that the flexible gasket on the end of the Metering Box creates an air tight seal around the grille The pressure reading t...

Page 9: ...xible tubing to the pressure tap located in the corner of the Metering Box Now connect the other end of the tubing to a pressure gauge If using a TEC digital pressure gauge connect the end of the tubi...

Page 10: ...1 E2 or E3 is determined by the position of the snap pin located on the top of the Metering Box The door position can be adjusted by pushing down on the snap pin and sliding the door until the snap pi...

Page 11: ...auge display will show SEL to indicate that a test device has not yet been selected The selected test device is chosen by toggling the SELECT switch up If the Display Shows Description SEL Begin flow...

Page 12: ...position on the Metering Box be sure to change the CONFIG setting on the gauge to match the new door position DG 3 The air flow reading from the exhaust fan will be shown directly on the gauge displa...

Page 13: ...to E2 or E3 adjust the position to create a larger opening in the Metering Box e g E1 or E2 If the door position is set to E1 the largest opening and the Metering Box pressure is still above 8 0 Pasc...

Page 14: ...10 4 8 96 45 22 1 2 48 23 11 5 0 98 46 23 1 4 52 25 12 5 2 100 47 23 1 6 55 26 13 5 4 102 48 23 1 8 59 28 14 5 6 103 49 24 2 0 62 29 14 5 8 105 50 24 2 2 65 31 15 6 0 107 51 25 2 4 68 32 16 6 2 109 5...

Page 15: ...tem Weight 4 lbs including the extension pole Dimensions Inside opening 13 x 16 x 8 deep The upper flow range limit of 124 CFM is based on the assumption that back pressures greater than 8 0 Pascals w...

Reviews: