12. Installation 

12.1 Before installation 

Please check whether the accessories are of full scope. If there are some fittings free from use, please restore them 
carefully. 

12.2 Installation space 

The indoor unit should be installed in a location that meets the following requirements: 

  There is enough room for installation and maintenance. 

  The ceiling is horizontal, and its structure can endure the weight of the indoor unit. 

  The outlet and the inlet are not impeded, and the influence of external air is the least. 

  The air flow can reach throughout the room. 

  The connecting water pipe and drainpipe could be extracted out easily. 

  There is no direct radiation from heaters. 

Caution:

 

Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 meter away from televisions and radios. 

This is to prevent image interference and noise in those electrical appliances. (Noise may be generated depending on the conditions under 
which the electric wave is generated, even if 1 meter is kept.)

 

12.3 Installation procedures for fresh air intake duct connection 

Preparing the connection hole 

  Cut off the knockout hole on the side plate with a nipper. 

  Cut the inner insulation of the hole portion with a cutter. 

Placing the insulation 

  Put the insulation tightly around the hole of the unit as shown. The ends of the side plate and the inner 

insulation must be completely adhered without leaving any clearance along the circumference of the hole. 
Make sure the inner surface of insulation tightly contacts the inner insulation edge and the side plate. (refer 
to fig.12.5) 

12.4 Install the main body 

A. The existing ceiling (to be horizontal) 

a.  Cut a quadrangular hole of 880×880mm in the ceiling according to the shape of the installation paper board. 

  The center of the hole should be at the same position of that of the air conditioner body. 

  Determine the lengths and outlets of the connecting pipe, drain pipe and cables. 

  To balance the ceiling and to avoid vibration, please enforce the ceiling when necessary. 

b.  Select the position of installation hooks according to the hook holes on the installation board. 

  Drill four holes of Ø12mm, 50~55mm deep at the selected positions on the ceiling. Then embed the 

expansible hooks (fittings). 

  Face the concave side of the installation hooks toward the expansible hooks. Determine the length of the 

installation hooks from the height of ceiling, and then cut off the unnecessary part. 

  If the ceiling is extremely high, please determine the length of the installation hook according to facts. 

c.  Adjust the hexangular nuts on the four installation hooks evenly, to ensure the balance of the body. 

  If the drainpipe is awry, leakage will be caused by the malfunction of the water-level switch. 

  Adjust the position to ensure the gaps between the body and the four sides of ceiling are even. The body's 

lower part should sink into the ceiling for 10~12 mm (refer to fig.12.6). 

  In general, L is half of the screw length of the installation hook. (refer to fig.12.6) 

  Locate the air conditioner firmly by wrenching the nuts after having adjusted the body's position well. (refer 

to fig.12.7) 

B. New built houses and ceilings 

a.  In the case of new built house, the hook can be embedded in advance (refer to the A.b mentioned above). But it 

should be strong enough to bear the indoor unit and will not become loose because of concrete shrinking. 

Summary of Contents for SFC1200A1

Page 1: ...220 240V 50Hz...

Page 2: ...50Hz AC Fan Coil Unit 2 Pipe Cassette Series Technical Service Manual...

Page 3: ...NCLATURE 2 2 PRODUCT SCHEDULE 3 3 EXTERNAL APPEARANCE 3 4 FEATURES 4 5 SPECIFICATIONS 5 6 DIMENSION 8 7 SOUND LEVELS 9 8 SERVICE SPACE 9 9 WIRING DIAGRAM 10 10 CAPACITY TABLES 15 11 EXPLODED VIEW 27 1...

Page 4: ...Heater Four way Cassette SFC600A1 600 220 240V 1Ph 50Hz Without SFC750A1 750 SFC850A1 850 SFC950A1 950 SFC1200A1 1200 SFC1500A1 1500 Compact Four way Cassette SFC300 300 220 240V 1Ph 50Hz Without 400...

Page 5: ...t operation and high efficiency Remote controller with LED display wired controller is optional Safety grill for safety maintenance Built in drain water pump For four way cassette the pump head is 750...

Page 6: ...h a x row pitch b mm 21 13 37 Fin spacing mm 1 5 Fin type Hydrophilic aluminum Coil length x height x width mm 1960 168 26 74 1960 168 26 74 1960 252 26 74 Max Working Pressure MPa 1 6 Circuit 8 8 12...

Page 7: ...mm 7 Row 2 2 3 Tube pitch a x row pitch b mm 21 13 37 Fin spacing mm 1 5 Fin type Hydrophilic aluminum Coil length x height x width mm 1960 252 26 74 1960 252 26 74 2080x252x40 11 Max Working Pressur...

Page 8: ...itch a x row pitch b 21 13 37 Fin spacing 1 3 Fin type Hydrophilic aluminum Length x Height x Width 1315 210 26 74 1315 210 26 74 1315 210 26 74 Max Working Pressure MPa 1 6 Circuit 5 6 7 Panel Net Di...

Page 9: ...sion Four way Cassette Model A B C D E F 600A1 750A1 180 140 85 350 145 195 850A1 950A1 1200A1 1500A1 180 140 155 350 155 205 Compact Four way cassette H 45mm Four way cassette H 50mm Compact four way...

Page 10: ...er three fan speed dB A H M L Four way Cassette SFC600A1 45 41 36 46 42 37 47 43 28 48 44 39 49 45 40 50 46 41 Compact Four way Cassette 36 33 28 42 39 32 45 42 34 8 Service Space SFC750A1 SFC850A1 SF...

Page 11: ...1 The CN3 port is closed that remote shutdown all control is invalid The CN3 port open remote start reply to this port closed state 2 Two control models is only connected with a vale the cold water va...

Page 12: ...P PUMP T1 ROOM TEMP SENSOR T2 C T2 H PIPE TEMP SENSOR XP1 5 XS1 5 CONNECTOR V1 THE COLD WATER VALVE V2 THE HOT WATER VALVE XT1 7 WAY TERMINAL ENC1 SW2 SWITCH FOR NETWORK ADDRESS SETTING 0 F of the ENC...

Page 13: ...The CN3 port open remote start reply to this port closed state 2 Two control models is only connected with a vale the cold water valve Four control models are respectively connected with the cold wat...

Page 14: ...P PUMP T1 ROOM TEMP SENSOR T2 C T2 H PIPE TEMP SENSOR XP1 5 XS1 5 CONNECTOR V1 THE COLD WATER VALVE V2 THE HOT WATER VALVE XT1 7 WAY TERMINAL ENC1 SW2 SWITCH FOR NETWORK ADDRESS SETTING 0 F of the ENC...

Page 15: ...NAME CAP1 INDOOR FAN CAPACITY CN1 20 P1 8 P C BOARD SOCKETS TRANS POWER TRANSFORMER FAN1 INDOOR FAN MOTOR K3 WATER LEVEL SWITCH M SWING MOTOR P PUMP T1 ROOM TEMPERATURE SENSOR T2 C PIPE TEMPERATURE S...

Page 16: ...3 76 0 51 6 4 4 61 3 50 0 57 8 0 5 05 3 24 0 62 9 5 5 40 3 04 0 66 10 9 9 3 5 54 3 65 1 59 62 5 4 88 4 13 1 40 48 4 5 39 3 83 1 54 59 1 5 85 3 59 1 68 69 6 6 23 3 41 1 78 78 9 4 5 23 3 52 1 12 31 3 4...

Page 17: ...2 4 71 1 90 62 5 7 18 4 41 2 06 73 7 7 65 4 18 2 19 83 5 4 6 42 4 32 1 38 33 2 5 64 4 92 1 21 25 5 6 23 4 57 1 34 31 2 6 77 4 29 1 46 36 8 7 25 4 03 1 56 42 3 5 6 08 4 14 1 05 19 0 5 21 4 81 0 90 14 0...

Page 18: ...87 4 89 1 97 67 0 7 46 4 58 2 14 79 0 7 94 4 34 2 28 89 5 4 6 67 4 49 1 43 35 5 5 85 5 11 1 26 27 4 6 47 4 74 1 39 33 4 7 03 4 46 1 51 39 4 7 53 4 19 1 62 45 3 5 6 32 4 30 1 09 20 4 5 41 4 99 0 93 15...

Page 19: ...5 7 77 5 53 2 23 77 4 8 43 5 18 2 42 91 2 8 98 4 91 2 57 103 4 4 7 54 5 08 1 62 41 1 6 62 5 78 1 42 31 6 7 32 5 36 1 57 38 6 7 95 5 04 1 71 45 6 8 52 4 73 1 83 52 3 5 7 14 4 86 1 23 23 5 6 12 5 65 1...

Page 20: ...0 115 6 8 89 7 53 2 55 89 5 9 82 6 99 2 82 109 2 10 66 6 55 3 06 128 7 11 35 6 21 3 25 145 8 4 9 54 6 42 2 05 57 9 8 37 7 30 1 80 44 6 9 25 6 78 1 99 54 5 10 05 6 37 2 16 64 3 10 76 5 98 2 31 73 8 5 9...

Page 21: ...11 49 8 41 2 47 49 5 12 47 7 91 2 68 58 4 13 37 7 43 2 87 67 1 5 11 21 7 63 1 93 30 2 9 61 8 86 1 65 22 2 10 85 8 13 1 87 28 3 11 82 7 58 2 03 33 6 12 71 7 09 2 19 38 9 6 10 46 7 35 1 50 18 3 8 88 8 5...

Page 22: ...84 2 02 0 81 34 7 3 08 1 89 0 88 40 9 3 28 1 79 0 94 46 4 4 2 75 1 85 0 59 18 4 2 42 2 11 0 52 14 2 2 67 1 96 0 57 17 3 2 90 1 84 0 62 20 5 3 11 1 73 0 67 23 5 5 2 61 1 77 0 45 10 6 2 23 2 06 0 38 7...

Page 23: ...49 1 00 37 2 3 80 2 33 1 09 43 9 4 04 2 21 1 16 49 7 4 3 40 2 29 0 73 19 7 2 98 2 60 0 64 15 2 3 29 2 41 0 71 18 6 3 58 2 27 0 77 21 9 3 83 2 13 0 82 25 2 5 3 21 2 19 0 55 11 3 2 75 2 54 0 47 8 3 3 1...

Page 24: ...16 0 78 16 2 4 01 2 94 0 86 19 8 4 35 2 76 0 94 23 4 4 66 2 59 1 00 26 8 5 3 91 2 66 0 67 12 1 3 35 3 09 0 58 8 9 3 79 2 84 0 65 11 3 4 12 2 64 0 71 13 4 4 44 2 47 0 76 15 5 6 3 65 2 56 0 52 7 3 3 10...

Page 25: ...PD TH WF WPD TH WF WPD TH WF WPD TH WF WPD 10 4 2 0 4 2 0 6 6 0 6 5 0 9 1 0 8 9 6 11 5 1 0 15 2 13 9 1 2 22 2 16 3 1 4 30 7 18 7 1 6 40 2 21 0 1 8 51 0 8 4 6 0 5 3 9 7 2 0 8 9 4 9 7 1 0 16 9 12 1 1 2...

Page 26: ...6 6 1 75 0 25 3 6 2 55 0 37 7 7 3 30 0 47 13 0 4 10 0 59 20 0 4 87 0 70 28 3 5 64 0 81 37 8 6 36 0 91 48 1 7 17 1 03 61 1 t Air inlet temp 20 DB Water inlet temp 35 40 45 50 55 60 65 70 TH WF WPD TH W...

Page 27: ...26 Altitude modification coefficient table Altitude m TC SC TH 500 0 98 0 95 0 95 1000 0 97 0 91 0 91 1500 0 95 0 86 0 86 2000 0 94 0 82 0 82 2500 0 93 0 78 0 78 3000 0 91 0 74 0 7...

Page 28: ...27 11 Exploded View Four way Cassette SFC600A1 SFC750A1 SFC850A1 SFC950A1 SFC1200A1 SFC1500A1...

Page 29: ...ubassembly drain tray 1 25 Water finder cover subassembly 1 6 Fan assembly 1 26 Front barrier III subassembly 1 7 Evaporator fixing board 1 26 1 Install lifting lug 4 8 Evaporator assembly 1 27 Water...

Page 30: ...29...

Page 31: ...y 1 25 Fan fixer 1 5 Foam subassembly drain tray 1 26 Water finder cover subassembly 1 6 Fan assembly 1 27 Front barrier III subassembly 1 7 Evaporator fixing board 1 27 1 Install lifting lug 4 8 Evap...

Page 32: ...nage pan ass y 1 4 Wire box 1 21 1 Plug 1 5 Cover box 1 22 E part box ass y 1 6 Remote controller 1 22 1 Main control board ass y 1 7 Temp sensor ass y 1 22 2 Transformer 1 8 Remote controller holder...

Page 33: ...4 Install the main body A The existing ceiling to be horizontal a Cut a quadrangular hole of 880 880mm in the ceiling according to the shape of the installation paper board The center of the hole sho...

Page 34: ...ntal of ceiling when installing it Refer to the A a mentioned above for others c Refer to the A c mentioned above for installation d Remove the installation paper board Caution After installing the bo...

Page 35: ...nstallation covers and remove them refer to fig 12 10 3 Install the panel a Align the swing motor on the panel to the tubing joints of the body properly b Fix hooks of the panel at swing motor and its...

Page 36: ...in and coagulation Prevent from water backflow into unit inside during shutdown the drain pipe shall place down side and drain water to outdoor drain side the gradient of the drain pipe should be hig...

Page 37: ...arate power supply with rated voltage The external power supply to the air conditioner should have ground wiring which is linked to the ground wiring of the indoor and outdoor unit The wiring work sho...

Page 38: ...ith their respective marked numbers on the terminal block of indoor and outdoor units Re install the cover or the protection board AIR FLOW m3 h 510 2550 POWER PHASE 1 phase FREQUENCY AND VOLT 220 240...

Page 39: ...38 Wiring figure...

Page 40: ...g on the power According to the user s requirement install the remote controller frame where the remote controller s signal can reach the indoor unit smoothly Test operation Set the air conditioner un...

Page 41: ...IPX0...

Reviews: