background image

 

1/8 

NOTICE

 

D’INSTALLATION

 

INSTALLATION MANUAL

 

 

 

 

 
 
 
 

 

 
 
 
 
 

 

 

1. 

Interface optique / 

Optical interface

 

 

4. 

LEDs de signalisation / 

Status LEDs

 

2. 

Bornier RS485 / 

RS485 connector

 

 

ON 

Vert fixe / 

Green Fixed

 

Produit opérationnel / 

Unit Operational

 

3. 

Connecteur Ethernet / 

Ethernet connector

 

 

Vert clignotant / 

Green blinking

 

Communication en cours / 

Ongoing communication

 

 

 

 

 

Rouge fixe / 

Red fixed

 

Ordre de phase incorrect /

 

Phase order wrong

 

 

 

 

 

1) Rouge clignotement lent / 

Red slow 

blinking 

2) Rouge clignotement rapide / 

Red fast 

blinking

 

1) Sortie(s) analogique(s) en dépassement / 

Analog 

output(s) overrange

 

2) Sortie(s) analogique(s) saturée(s) / 

Analog output(s) 

overloaded

 

 

 

 

 

Rouge fixe / 

Red fixed

 

Sortie(s) analogique(s) forcée(s) / 

Analog output(s) 

forced

 

 

Sécurité / 

Safety

 

Vous venez d’acquérir un transducteur numérique du type 

TRIAD 2

 et nous vous remercions de votre confiance. 

Cet appareil est destiné à  être utilisé dans les installations de 

CAT III 300V

, degré de pollution 2, conformément aux 

dispositions de la norme CEI 61010-1 et CEI 61010-2-030. 

Pour  installer  votre  appareil  dans  les  meilleures  conditions,  lisez  attentivement  cette  notice  d’installation  et  respectez  les 
précautions d'installation, qui y sont mentionnées. 
L’appareil décrit dans ce manuel est destiné à  être exclusivement utilisé par un personnel  habilité et préalablement formé.  Afin 
que la protection assurée par cet appareil ne soit pas compromise, celui-ci doit être utilisé conformément à cette notice. 
Ce  produit  est  un  convertisseur  alimenté  par  ses  voies  mesures,  et  ne  comporte  pas  d’interrupteur  pour  sa  mise  hors  tension. 
L’installation électrique doit donc : 

 

Inclure un interrupteur ou un disjoncteur, de préférence proche du convertisseur 

 

Prévoir que cet interrupteur ou disjoncteur soit placé convenablement et facilement accessible 

 

Prévoir que cet interrupteur ou disjoncteur soit marqué comme étant le dispositif de coupure de l'appareil 

Pour  nettoyer  votre  appareil  déconnectez-le  du  réseau  électrique  et  de  son  alimentation  auxiliaire,  utilisez  exclusivement  un 
chiffon sec pour nettoyer la surface extérieure. Il ne faut pas utiliser de produits abrasifs, ni de solvants et en aucun cas mouiller 
les bornes de branchement. 
 

Thank you for buying this 

TRIAD 2

 digital transducer. 

This device is intended for use under the conditions of installation 

CAT III 300V

, degree of pollution 2, in accordance with the 

provisions of IEC standard 61010-1 and CEI 61010-2-030. 
To install your device  in the best condition

,

  read this installation  manual carefully  and observe  the precautions it recommends. 

The device is intended for use only by accredited and properly trained staff and for safety reasons, must be used according to the 
following instructions. 

16, Rue Georges Besse – Silic 44 
92182 ANTONY cedex – France 
Tél. +33 (0)1 75 60 10 30 
Fax. +33 (0)1 46 66 62 54 

http://www.enerdis.fr

 

 

 

MS01-7397 / 03 

Ed. 05/04/2016

 

Summary of Contents for TRIAD 2

Page 1: ...assur e par cet appareil ne soit pas compromise celui ci doit tre utilis conform ment cette notice Ce produit est un convertisseur aliment par ses voies mesures et ne comporte pas d interrupteur pour...

Page 2: ...t be returned to your distributor Pr cautions d installation Installation precautions A r ception de l appareil contr ler qu il est intact et n a subi aucun dommage pendant le transport Lorsque l on s...

Page 3: ...T3 57 7 Vac to 276 Vac max ph n 480 Vac max ph ph Fr quence Frequency 50 Hz 42 5 57 5 Hz 60 Hz 51 69 Hz Tension au primaire max Max primary voltage measured 1 MV ph ph Surcharge admissible Acceptable...

Page 4: ...ommand e Vous trouverez ci apr s les principaux sch mas de raccordement des entr es de mesure au r seau lectrique We strongly recommend the use of fuses on the voltage inputs and of short circuitors o...

Page 5: ...5 8 Branchement sur r seau triphas quilibr 4 fils Balanced three phase network 4 wires Branchement sur r seau triphas non quilibr 3 fils Unbalanced three phase network 3 wires...

Page 6: ...rs de tension primaire isol pour installation haute tension 3 single pole insulated voltage transformers in high voltage system Branchement sur r seau triphas non quilibr 4 fils Unbalanced three phase...

Page 7: ...twork Raccordements Connections Ent es sorties et alimentation Inputs outputs and Auxiliary supply Alimentation non polaris e Non polarized auxiliary supply RS485 Ethernet Vaux Neutral L1 L2 L3 S1 S2...

Page 8: ...s entr es sorties de votre produit ainsi que le sch ma de raccordement correspondant votre installation lectrique Pour imprimer ces tiquettes il vous faut raccorder votre TRIAD 2 un PC par l interm di...

Reviews: