Enerco HSVFB20LPT Installation Instructions And Owner'S Manual Download Page 5

5

Installation Instructions and Owner’s Manual

Unvented LP-Gas Vent Free Room Heaters

*Adjoining rooms are communication only if there 

are doorless passageways or ventilation grills be

-

tween them.

DETERMINING THE TYPE OF HEATER 

LOCATION SPACE:

Use this method to determine if you have a confined or 

unconfined space.

Note:

 the space includes the room in which you 

install heater plus any adjoining rooms with doorless 

passageways or ventilation grills between the rooms.

1. Find the volume of the space by multiplying room 

length x width x height.

Example: Space size 18ft (length) x 18ft. (width) x 8ft.  

 

(height) = 2592

If additional ventilation to adjoining room is supplied 

with grills or openings, add the volume of these rooms 

to the total volume of the space.
2. Divide the space volume by 50 cubic feet to deter

-

mine the maximum Btu/hr the space can support.

Example: 2592 cu.ft. (volume of space) / 50 cu.ft. =  

 

51.8 or 51,800 (maximum Btu/hr the space  

 

can support)

WARNING:

 If the area in which the heater may be 

operated is smaller than defined as an unconfined 

space or if the building is of unusually tight con

-

struction, provide adequate combustion and ventila

-

tion air by the methods described in the 

National 

Fuel Gas Code, NFPA 54/ ANSI Z223.1, 

Section 

5.3 or applicable local codes. 

3. Add the Btu/hr of all the fuel-burning appliances 

in the space such as, Vent–free heater, Gas water 

heater, Gas furnace, Vented gas heater, Gas fire

-

place logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-

vent draws combustion air from the outdoors and 

vents to the outdoors.
Example:  Gas water heater 

40,000 Btu/hr

 

 

Vent Free  

20,000 Btu/hr

 

 

Total   

 

=60,000 Btu/hr

4. Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.

Example:   51,800 Btu/hr (maximum Btu/hr the  

 

 

space can support)

 

 

60,000 Btu/hr (Actual amount of Btu/hr  

 

 

used)

The space in the above example is a confined 

space because the actual Btu/hr used is more than 

the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options 

are as follows:

A. Rework worksheet, and the space of an adjoining 

room. If the extra space provides an unconfined 

space, remove door to adjoining room or add venti

-

lation grills between the rooms. See Ventilation Air 

From Inside Building (Figure 2).

B. Vent room directly to the outdoors. See Ventilation 

Air From Outdoors (Figure 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size 

makes room unconfined. 

If actual Btu/hr used is less than the maximum Btu/

hr the space can support, the space is an uncon

-

fined space. You will need no additional fresh air 

ventilation.

VENTILATION AIR
Ventilation from Inside Building

This fresh air would come from an adjoining unconfined 

space. When ventilation to an adjoining unconfined 

space, you must provide two permanent openings: one 

within 12” of the ceiling and one within 12” of the floor 

on the wall connecting the two spaces (see options 1 

& 2 of fig. 2). You can also remove door into adjoin

-

ing room (see option3, fig 2). Follow the National Fuel 

Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for 

Combustion and Ventilation for required size of ventila

-

tion grills or ducts.

Figure 2.

Figure 3.

Ventilation 

Gills into 

Adjoining 

Room - 

Option 1

Ventilation Gills into 

Adjoining Room - Option 2

12”

12”

Or remove 

door into 

Adjoining 

Room - 

Option 3

INLET 

AIR

OUTLET 

AIR

VENTILATION CRAWL SPACE

TO CRAWL 

SPACE

TO ATTIC

VENTILATION AIR

VENTILATED 

ATTIC

OUTLET AIR

Summary of Contents for HSVFB20LPT

Page 1: ...ovisions for adequate combustion and ventilation air must be provided Refer to Fresh Air for Combustion and Ventilation section on page 4 of this manual WARNING Improper installation adjustment altera...

Page 2: ...hildren and adults away from hot surfaces to avoid burns or clothing igni tion Heater will remain hot for a time after shutdown Allow heater surfaces to cool before handling Young children should be c...

Page 3: ...6 3 Keep all air openings in heater clear free of debris or any blockage This will insure that enough air for proper combustion enters the heater 4 If heater shuts off do not relight until you provide...

Page 4: ...l Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Com bustion and Ventilation All spaces in homes fall into one of the three following ventilation classifications 1 Unusually Tight Construction 2 Unc...

Page 5: ...Vent Free Heater 20 000 Btu hr Total 60 000 Btu hr 4 Compare the maximum Btu hr the space can support with the actual amount of Btu hr used Example 51 800 Btu hr maximum Btu hr the space can support 6...

Page 6: ...pos sible provide greater clearances from the floor ceil ing and joining walls WARNING Rework worksheet adding the space of the adjoining unconfined space The combined space must have enough fresh ai...

Page 7: ...ll be located Make sure mounting bracket is level For wall stud mounting locate one end of the mounting bracket over a wall stud WARNING Maintain minimum clearances shown in figure 7 If you can provid...

Page 8: ...bottom mounting screw into wall stud drill holes at marked locations using 9 64 drill bit 5 Re place heater onto mounting bracket 6 Place spacers between bottom mounting holes and wall anchor or drill...

Page 9: ...o 14 W C Pressure Tee Joint 1 8 NPT Plug Tap Cap Pipe Nipple Tee Joint 3 8 NPT Pipe Nipple Sediment Trap Test Gauge Connection Reducer Bushing to 1 8 NPT 3 Minimum CAUTION Use pipe joint sealant that...

Page 10: ...TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the...

Page 11: ...t cleaning due to excess lent from carpeting bedding material pet hair etc Make sure grille guard is in place before running heater If screen or grille guard is removed for servicing it must be replac...

Page 12: ...uum cleaner pressurized air or small soft bristled brush to clean CLEANING BURNER PILOT AIR HOLE INLET We recommend that you clean the unit ever 2 500 hours of operation or every three months We also...

Page 13: ...13 Installation Instructions and Owner s Manual Unvented LP Gas Vent Free Room Heaters This page intentionally left blank...

Page 14: ...regulator 6 Turn Control knob to pilot position When ignitor button is pressed in there is a spark at the ODS pilot but no ignition 1 Control knob not fully pressed in 2 Control knob not pressed in lo...

Page 15: ...ee Figure 4 page 7 4 Clean burner orifice see Cleaning and Maintenance on pages 11 and 12 or replace burner orifice White powder residue forming within burner box or on adjacent walls or furni ture 1...

Page 16: ...eaters IR20LPT IR30LPT BF20LPT BF30LPT 7 2 36 39 38 35 16 21 16 1 16 2 6 26 29 24 22 3 13 23 18 3 11 1 2 1 4 22 2 33 1 22 1 25 9 5 1 3 1 1 27 1 28 1 4 44 42 45 8 20 10 15 14 42 9 7 26 22 3 22 1 33 1 1...

Page 17: ...Thermostat Valve assembly 1 9 70641 70641 70641 70641 Ignitor Module Mounting Bracket 1 10 70682 70682 70682 70682 High Limit Switch 1 11 70644 70644 70644 70644 Ignitor Module Battery powered 1 12 70...

Page 18: ...in Relief Grommet 1 70689 70692 Right Burner Gas Tube 1 70690 70693 Right Middle Gas Burner Tube 1 70598 Left Middle Gas Burner Tube 1 70691 70694 Left Burner Gas Tube 1 70695 70695 70696 70696 ODS Ga...

Page 19: ...19 Installation Instructions and Owner s Manual Unvented LP Gas Vent Free Room Heaters This page intentionally left blank...

Page 20: ...ctory FOR INFORMATION REGARDING SERVICE Please call Toll Free 800 251 0001 www mrheater com Our office hours are 8 30 AM 5 00 PM EST Monday through Friday Please include the model number date of purch...

Reviews: