eNeRCo GRoUP, INC. |Indirect Fired Portable Heater

operating Instructions and owner’s manual

CoNTRol lAmP

CONTROL KNOB HEAT - STOP - VENTILATION ONLY

PoWeR CoRD FAsTeNeR

oVeRHeAT sAFeTY THeRmosTAT, l1

FAN THeRmosTAT, F

LIMIT THERMOSTAT WITH MANUAL RESTART, L2

THeRmosTAT ReseT sWITCH

HoUR CoUNTeR

OVERHEAT THERMOSTATS CONTROL LAMP, L1, L2

10 

FAN sToP CoNTRol lAmP

11 

HeATeD DIesel FIlTeR PlUG

12 

BURNeR PlUG

13 

Room THeRmosTAT PlUG

Control Board

INSTALLATION

wARNINg

 THe FolloWING oPeRATIoNs mUsT Be CARRIeD oUT 

BY QUAlIFIeD PeRsoNNel oNlY.

Electrical Connections Settings

every space heater is supplied along with the safety and control 
devices which are indispensable to the correct functioning of 
the unit. The electric switchboard, burner, the fan thermostat, 
overheat safety thermostat and the overheat thermostat with 
manual restart have already been connected.

wARNINg

 PoWeR sUPPlY CoRD oF PRoPeR DImeNsIoN 

sHAll Be CoNNeCTeD To THe mAIN sWITCHBoARD 
AND HeATeR sHAll Be GRoUNDeD. eleCTRICAl 
GRoUNDING sHAll Be IN ComPlIANCe WITH THe 
NATIoNAl eleCTRICAl CoDe ANsI/NFPA 70 oR THe 

CSA C22.1 CANADIAN ELECTRICAL CODE, PART I.

The following operations must now be carried out:

• Plug in the power cord having read the adhesive label which 

details electricity supply characteristics.

• The burner must be connected to the fuel supply (Burner 

Instruction manual).

• Connect the burner to the electricity supply with the burner 

plug. 

• Connect accessories such as the room thermostat or clock to 

the unit’s electric switchboard with the thermostat plug.

Having completed all these operations check carefully that all 

electrical connections correspond to the wiring diagram. When 

the heater is first turned on you must check that the fan does not 

use more current than the maximum permitted limit.

Finally, to regulate the burner, follow the instructions in the Burner 
Instruction manual.

INSTRUCTIONS FOR USE

Switching On

• Set the control knob (2) in position “0”.
• Turn on the disconnecting switch on the electric 

switchboard.

• If the unit is operated manually turn the control knob to

The burner starts up, the combustion chamber heats up and 
then the fan starts.

• If the unit operates automatically set the room thermostat 

at the desired level and turn the control knob (2) to 

: the 

heater will now start and stop automatically.

• If the heater doesn’t start after you have completed the 

above operations consult the Troubleshooting section of this 
manual.

Turning Off

In manual operation turn control knob (2) to “0” or turn off 

control in automatic operation.

The burner stops while the fan turns itself on and off until the 
combustion chamber has completely cooled down.

Summary of Contents for Heatstar 4000ID

Page 1: ...4135 800 251 0001 INDIRECT FIRED Space HEATER heatstar BY eNERCO If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or los...

Page 2: ...TRUCTIONS SHOULD USE OR SERVICE THIS HEATER IF YOU NEED ASSISTANCE OR HEATER INFORMATION SUCH AS AN INSTRUCTIONS MANUAL LABELS ETC CONTACT THE MANUFACTURER WARNING NOT FOR HOME OR RECREATIONAL VEHICLE...

Page 3: ...maximum level of heat output of the furnace TECHNICAL SPECIFICATIONS TABLE To make sure that there is adequate air circulation and air supply to the heater and that nothing is obstructing the aspirat...

Page 4: ...e adhesive label which details electricity supply characteristics The burner must be connected to the fuel supply Burner Instruction Manual Connect the burner to the electricity supply with the burner...

Page 5: ...ced by other types of head with two or four openings which allow for flexible tubes in heat distribution The screws which hold the original outlet in place should be removed and the new outlet should...

Page 6: ...s Code ANSI Z223 1 NFPA and the Natural Gas and Propane Installation Code CSA B149 1 In case of connection of heater to propane supply cylinder the installation shall conform with local codes or in th...

Page 7: ...t 10 lights up Fan motor current absorption is excessive Heater with helicoidal ventilator remove eventual debris preventing free flow of air on intake and outlet Check length of air ducts reduce if e...

Page 8: ...ng Diagram 4000iD Series Models m Fan Motor f Fan Thermostat l1 Overheat Safety Thermostat l2 Limit Thermostat with Manual Restart rv Control Knob Ventilation Only br Burner ta Room Thermostat fb Burn...

Page 9: ...le Heater Wiring Diagram 4000iD and 7000iD Series Models ts Fans Thermal Relay tm Fans Tele contactor c Condenser Motor pa Room Thermostat Plug re Relay 220V 60Hz sb Fan Stop Control Lamp pb Steckdose...

Page 10: ...ble Heater Operating Instructions and Owner s Manual 4000ID and 7000ID Series Indirect Fired Space Heater 04 03 17 22 19 05 20 06 23 21 8 25 07 09 24 10 12 31 29 16 27 32 30 46 15 18 26 26 28 11 91 10...

Page 11: ...table Heater 4000ID and 7000ID Series Indirect Fired Space Heater 84 88 85 86 87 64 62 58 60 57 63 61 59 R 90 91 95 96 105 94 101 103 101 102 100 99 106 104 92 107 89 97 R 98 93 70 67 69 66 75 74 73 7...

Page 12: ...9010 Upper long OX angle steel G01738 9010 22 G01833 9010 Vertical front SX angle steel G01740 9010 no Stock No 4000 7000 Description 23 G01834 9010 Vertical front OX angle steel G01742 9010 24 G01835...

Page 13: ...V230 76 E20626 Thermostat plug 3P T 77 E20627 Plate plug 3P T 78 E20629 Thermostat plug 4P T 79 G00216 Plate plug 4P T G00217 80 E1 1 120 Relay Finder 65 31 AC 81 G04207 Relay flange 82 E20639 Thermo...

Page 14: ...nsportation prepaid within said one year period and found by the Company to have imperfections in material or workmanship If a part is damaged or missing call our Technical Support Department at 800 2...

Page 15: ...au fabricant dans la p riode de un an et jug s par l entreprise comme pr sentant des d fauts de mat riel ou de main d uvre Si une pi ce est endommag e ou manquante composez le 1 800 251 0001 Adressez...

Page 16: ...6 E20626 FICHE DE THERMOSTAT 3P T 77 E20627 PLAQUE DE PRISE 3P T 78 E20629 FICHE DE THERMOSTAT 4P T 79 G00216 PLAQUE DE PRISE 4P T G00217 80 E1 1 120 RELAIS FINDER 65 31 AC 81 G04207 BRIDE DE RELAIS 8...

Page 17: ...GUE DROITE G01738 9010 22 G01833 9010 CORNI RE VERTICALE C T BR LEUR GAUCHE G01740 9010 N N DE 4000 7000 DESCRIPTION 23 G01834 9010 CORNI RE VERTICALE C T BR LEUR DROITE G01742 9010 24 G01835 9010 COR...

Page 18: ...ustion indirecte G n rateurs d air chaud portables combustion indirecte mod les 4000ID et 7000ID 84 88 85 86 87 64 62 58 60 57 63 61 59 R 90 91 95 96 105 94 101 103 101 102 100 99 106 104 92 107 89 97...

Page 19: ...e Guide d utilisation et instructions de fonctionnement G n rateurs d air chaud portables combustion indirecte mod les 4000ID et 7000ID 04 03 17 22 19 05 20 06 23 21 8 25 07 09 24 10 12 31 29 16 27 32...

Page 20: ...LECTRIQUE MOD LES 4000ID ET 7000ID TS Relais thermique des ventilateurs TM T l rupteur de ventilateur C Moteur du condenseur PA Prise thermostat d ambiance RE Relais 220 V 60 Hz SB T moin d arr t du v...

Page 21: ...E 4000ID M Moteur de ventilateur F Thermostat de ventilateur L1 Thermostat de s curit de surchauffe L2 Thermostat de s curit r armement manuel RV Commutateur Ventilation uniquement BR Br leur TA Therm...

Page 22: ...me Appel de courant excessif du moteur de ventilateur G n rateurs ventilateur h lico dal retirer tout corps tranger pouvant nuire au passage de l air dans l aspiration ou la sortie d air V rifi er la...

Page 23: ...FPA aux tats Unis et aux r glements du code d installation du propane et du gaz naturel CSA B149 1 au Canada Pour relier le g n rateur une bonbonne de propane l installation devra tre effectu e confor...

Page 24: ...ir chaud Le diffuseur fourni avec chaque appareil peut tre remplac par d autres types deux ou quatre orifi ces destin s recevoir les buses de raccordement des conduits de distribution de chaleur Pour...

Page 25: ...ues de l tiquette appos e sur l appareil le branchement du br leur la ligne d alimentation du combustible conform ment au guide d utilisation du br leur le branchement lectrique du br leur au moyen de...

Page 26: ...puissance thermique maximale de la chambre de combustion voir la section CARACT RISTIQUES TECHNIQUES Assurez vous que le d bit d air ne soit pas inf rieur au d bit nominal V rifi ez cette fi n qu aucu...

Page 27: ...UTILISER OU EFFECTUER L ENTRETIEN DE CET APPAREIL DE CHAUF FAGE SI VOUS AVEZ BESOIN D AIDE OU D INFORMATION AU SUJET DE L APPAREIL DE CHAUFFAGE MANUEL D INS TRUCTIONS TIQUETTES ETC VEUILLEZ COMMUNI Q...

Page 28: ...RATEUR D AIR CHAUD PORTABLE COMBUSTION INDIRECTE HEATSTAR D ENERCO Le fait de ne pas respecter la lettre les instructions du pr sent guide risque d entra ner une explosion ou un incendie causant des...

Reviews: