Modbus parameters
8.4.2
EtherNet/IP via Ethernet
You do not need to make any settings for the EtherNet/IP protocol.
8.4.3
HART via Ethernet or RS-485
The parameters contained in this leaf pertain to the set up of the HART communication to
the host on the interfaces offered by Fieldgate SWG70.
1. Click
Wired Communication => Protocols => HART
to display the associated
parameters:
2. If the default port number is changed, and FieldCare is in use, communication will be
lost.
3. Reconfigure the HART IP CommDTM communication parameters, before making
connection again. See Chapter 7.3.2 "Adding the Fieldgate SWG70" on page 38, Step 4.
Parameter
Meaning
Default
Bus Address Selection Specifies whether hardware (DIP switch 0-3) or software polling address
settings are to be used
Software
Bus Address
Sets the HART address of the wireless fieldgate when
Bus Address
Selection
is set to Software
– When DIP-Switch is selected, displays the setting
1
Baud Rate Selection
Specifies whether hardware (DIP switch 4–5) or software baudrate
settings are to be used
• DIP Switch Setting: 9600 Bit/s - 57600 Bit/s
• Software Setting: 1200 Bit/s - 115200 Bit/s
Software
Baud Rate
Sets the baudrate of the wireless fieldgate when Baud Rate Selection is set
to Software
– When DIP-Switch is selected, displays the setting
38400
Parity Bit
Sets the number of parity bits in the Modbus RTU telegram
• Odd, Even or None
Odd
Stop Bit
Sets the number of stop bits in the Modbus RTU telegram
• 1, 1.5 or 2
1
Port Number
(Ethernet)
Sets Fieldgate port number for Modbus TCP transmission
– If the port number is changed, the default port remains open
– Modbus TCP allows access for up to five masters
502