Operating Instructions

Thermophant T TTR31, TTR35

Temperature switch

BA00229R/09/EN/16.20

71509054

2020-10-15

Valid as of version

01.02 (device version)

Summary of Contents for Thermophant T TTR 35

Page 1: ...Products Solutions Services Operating Instructions Thermophant T TTR31 TTR35 Temperature switch BA00229R 09 EN 16 20 71509054 2020 10 15 Valid as of version 01 02 device version ...

Page 2: ......

Page 3: ...ansport 9 4 Mounting 9 4 1 Mounting requirements 9 4 2 Mounting the device 10 5 Electrical connection 12 5 1 Connecting requirements 12 6 Operating options 15 6 1 Local operation 15 6 2 Access to the operating menu via the operating tool 24 7 Diagnostics and troubleshooting 25 7 1 General troubleshooting 25 7 2 Firmware history 26 8 Maintenance 27 8 1 Cleaning 27 9 Repair 28 9 1 Return 28 9 2 Disp...

Page 4: ... this situation can result in serious or fatal injury CAUTION This symbol alerts you to a dangerous situation Failure to avoid this situation can result in minor or medium injury NOTICE This symbol contains information on procedures and other facts which do not result in personal injury 1 2 2 Electrical symbols Symbol Meaning Direct current Alternating current Direct current and alternating curren...

Page 5: ...Procedures processes or actions that are forbidden Tip Indicates additional information Reference to documentation A Reference to page Reference to graphic Notice or individual step to be observed 1 2 3 Series of steps Result of a step Help in the event of a problem Visual inspection 1 2 4 Symbols in graphics Symbol Meaning Symbol Meaning 1 2 3 Item numbers 1 2 3 Series of steps A B C Views A A B ...

Page 6: ...s designed to meet state of the art safety requirements and complies with applicable standards and EC regulations The device can however be a source of danger if used incorrectly or for anything other than the purpose for which it was intended The manufacturer is not liable for damage caused by using the device incorrectly or for purposes for which it was not intended 2 3 Workplace safety For work...

Page 7: ...ctory in a condition in which it is safe to operate It meets general safety standards and legal requirements It also complies with the EC directives listed in the device specific EC Declaration of Conformity Endress Hauser confirms this by affixing the CE mark to the device 2 6 IT security Our warranty is valid only if the device is installed and used as described in the Operating Instructions The...

Page 8: ...lustrated below is designed to help users identify specific product information such as the serial number design variables configuration and device approvals Thermophant T Order Code TTR3x xxxxxxxx Ser No xxxxxxxxxxxxxx TAG No Xxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxx Rel XX YY ZZ Pt100 50 150 C 40 C Ta 85 C IP6X Output 250 mA Current consump 60mA 12 30V DC PNP 4 20mA 1 4 3 2 L L 1 2 1 2 3 4 5 6 7 8 9...

Page 9: ...see Process connections section 39 3 A Authorization No 1144 3 A Sanitary Standard Permitted process connections in accordance with 3 A see also Process connections section 39 FDA compliant 3 7 Storage and transport Pack the device so that it is reliably protected against impact when it is stored and transported The original packaging offers the best protection Storage temperature 40 to 85 C 40 to...

Page 10: ...e switch 3 Temperature switch for use in hygienic processes 4 2 1 General installation instructions Installation at elbows against the direction of flow A Installation in smaller pipes inclined against the direction of flow B Installation perpendicular to the direction of flow C Installation of hygiene version at a min angle of 3 to guarantee self draining The local display can be rotated electron...

Page 11: ...self centering sealing ring 1 1 Sensor with milk pipe connection 1 2 Groove slip on nut 1 3 Counterpart connection 1 4 Centering ring 1 5 Sealing ring 2 Varivent and APV Inline LB LL HL connection 2 1 Sensor with Varivent connection 2 2 Counterpart connection 2 3 O ring 3 Clamp according to ISO 2852 DB DL connection EHEDG certified only in conjunction with seal according to EHEDG position paper 3 ...

Page 12: ...combination with tubing piping or tank vessel In the case of internal tank fixtures using process connection nozzles it is important to ensure that the cleaning assembly sprays this area directly so that it is cleaned properly 2 The Varivent connections enable flush mounted installation NOTICE The following action must be taken if a sealing ring O ring or seal fails The thermometer must be removed...

Page 13: ... 1x PNP switch output and 1x analog output 4 to 20 mA A4 1x analog output 4 to 20 mA and 1x PNP switch output m R2 A4 1x analog output 4 to 20 mA and 1x PNP switch output m diagnostics NC contact with DESINA setting LWARNING Observe the following to avoid damaging the analog input of a PLC Do not connect the active PNP switch output of the device to the 4 to 20 mA input of a PLC DESINA distributed...

Page 14: ...Electrical connection Thermophant T TTR31 TTR35 14 Endress Hauser 5 1 2 DC voltage version with valve connector 1 3 L L 2 R B A0035798 Item no Output setting B 1x PNP switch output ...

Page 15: ...ng menu 1 E 4 5 2 3 A0044663 5 Position of the operating elements and possibilities for display 1 Operating keys 2 Digital display illuminated white ok red alarm error 3 Yellow LED for switching states LED on switch closed LED off switch open 4 Communication jack for PC configuration 5 LED for status display green OK red error fault flashing red green warning To prevent damage to the keys do not o...

Page 16: ...t the Function with the E key 4 If software locking is enabled it must be disabled before making entries or changes Enter and change the parameters with the or key 5 Press the E key to return to Function 6 Press the E repeatedly to return to Function group until the relevant function group is reached 7 To return to the measuring position Home press the E key for longer than 3 s 8 To display the pr...

Page 17: ...C FNC2 SIM SIM2 PRES LOCK DISP DESI ZERO GET Z TAU SP SP2 RSP RSP2 TSP TSP2 MAX TRSP TRS2 MIN REV C LST A CODE C WINC WINC OFF OFF NO 0 PV NO 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 F HYNC HYNC OPEN OPEN YES PVRO YES SPRO K WINO WINO CLOS CLOS SP OFF HYNO HYNO OFFR E E E E A B C A0008102 7 Operating menu A function groups B functions C settings ...

Page 18: ... 6 1 3 Structure of the operating menu for 1x switch output and 1x analog output4 to 20 mA For devices with an analog output both output 1 and output 2 can be configured as an analog output It is also possible to configure output 1 and output 2 as a switch output ...

Page 19: ...ng options Endress Hauser 19 A0008103 8 Operating menu A function groups B functions C settings The function group 4 20 is available only if the 4 to 20 mAanalog output 4 20 is selected under FUNC or FNC2 in function group OUT or OUT2 ...

Page 20: ...f rotated by 180 Factory setting current measured value PV TAU Damping display value output signal 0 0 Damping of measured value or display value and output 0 no damping or 9 to 40 s in increments of 1 s Factory setting 0 s BASE DESI DESINA NO YES The PIN assignment of the M12 connector is in accordance with the guidelines of DESINA Factory setting NO DESINA can be selected only if output 1 and 2 ...

Page 21: ...etting is ordered Switch point SP1 45 C 113 F switchback point RSP1 44 5 C 112 1 F Switch point SP2 55 C 131 F switchback point RSP2 54 5 C 130 1 F Range of adjustment LRL Lower Range Limit URL Upper Range Limit LRV Lower Range Value URV Upper Range Value t t 1 2 3 4 T A B T SP SP RSP RSP 0 0 0 0 1 1 1 1 A0023240 9 Switch point functions A Hysteresis function B Window function 1 Window NC contact ...

Page 22: ...increments of 0 1 s Factory setting 0 s Minimum difference between SP and RSP 0 5 C K 0 9 F 6 1 6 Setting for output 1x switch output and 1x analog output 4 to 20 mA Function group Function Settings Description OUT Output 1 OUT2 Output 2 FUNC FNC2 Switching characteristics WINC HYNC WINO HYNO 4 20 WINC Window NC contact HYNC Hysteresis NC contact WINO Window NO contact HYNO Hysteresis NO contact 4...

Page 23: ...if the 4 to 20 mAanalog output 4 20 is selected under FUNC or FNC2 in function group OUT or OUT2 6 1 7 Setting the service functions Function group Function Settings Description SERV Service functions LOCK Locking code 0 Enter the locking code to enable the device CODE Change locking code 0 Freely selectable numerical code 1 to 9999 0 no locking A locking code that has already been assigned can on...

Page 24: ... configuration software 2 Configuration kit with USB port 3 Temperature switch 6 2 1 Additional operating options In addition to the operating options listed in the previous Local operation section further information about the temperature switch is available via the configuration software Function group Description SERV Number of switch changes output 1 Number of switch changes output 2 Device st...

Page 25: ...ess com 7 Diagnostics and troubleshooting 7 1 General troubleshooting If an error occurs in the device the color of the status LED changes from green to red and the lighting of the digital display from white to red A flashing red green status LED signals a warning The display shows An E code in the event of errors The measured value is uncertain if an error occurs A W code in the event of warnings...

Page 26: ...in the specified measuring range W209 Device starting up W210 Configuration changed warning code is displayed for approx 15 s W212 Sensor signal is outside the permitted range Operate device in the specified measuring range W250 Number of max switching cycles exceeded Replace device W270 Short circuit and overload at output 1 Check output wiring Increase the load resistance at switch output 1 W280...

Page 27: ...832 12 2004 01 01 00 New analog electronics BA201r 09 en 02 05 51009832 06 2004 01 00 00 Original firmware KA174r 09 en 51008031 8 Maintenance Buildup on the sensor negatively affects measurement accuracy Check the sensor for buildup at regular intervals LCAUTION Damage to the device Ensure that the process is unpressurized before you remove the device Do not twist the device out of the process co...

Page 28: ... and national legislation 1 Refer to the website for more information http www endress com support return material 2 Return the device if repairs or a factory calibration are required or if the wrong device was ordered or delivered 9 2 Disposal The device contains electronic components and must therefore be disposed of as electronic waste in the event of disposal When disposing comply with nationa...

Page 29: ... with pressure screw 51004751 Order number without pressure screw 51004752 G 25 0 98 36 1 42 30 1 18 6 0 24 4 3 2 1 AF24 A0020709 EN 11 Dimensions in mm in 1 Pressure screw 303 304 2 Washer 303 304 3 Sealing taper PEEK 4 Collar welding boss 316L 10 1 2 Collar welding boss Collar welding boss movable with sealing taper and washer Material of parts in contact with the process 316L PEEK Max process p...

Page 30: ... in C in mm in B in mm in Clampin g ring material Max process temperatur e Max process pressure TA50 G SW AF 27 47 1 85 15 0 6 SS316 1 800 C 1472 F 40 bar at 20 C 580 psi at 68 F PTFE 2 200 C 392 F 5 bar at 20 C 72 5 psi at 68 F G SW AF 32 63 2 48 20 0 8 SS316 1 800 C 1472 F 40 bar at 20 C 580 psi at 68 F PTFE 2 200 C 392 F 5 bar at 20 C 72 5 psi at 68 F G1 SW AF 41 65 2 56 25 0 98 SS316 1 800 C 1...

Page 31: ...installation 2 PTFE Elastosil clamping ring reusable once loosened the compression fitting can be moved up or down on the thermowell Fully adjustable immersion length 10 2 Communication specific accessories 10 2 1 Coupling connecting cable Coupling M12x1 straight Connection to M12x1 housing connector Materials body PA coupling nut CuZn nickel plated Degree of protection connected IP 67 Order numbe...

Page 32: ... 4 pin post connector Order code TXU10 AA Commubox FXA291 configuration kit with interface cable for PC with USB port Intrinsically safe CDI interface Endress Hauser Common Data Interface for transmitters with 4 pin post connector Suitable configuration software is FieldCare for example Order code FXA291 10 2 3 Configuration software The ReadWin 2000 and FieldCare Device Setup configuration progra...

Page 33: ... output and 4 to 20 mA output active 11 2 2 Signal on alarm Analog output 3 6 mA or 21 0 mA if setting is 21 0 mA output is 21 5 mA Switch outputs in safe state switch open 11 2 3 Load Max Vpower supply 6 5 V 0 022 A current output 11 2 4 Range of adjustment Switch output Switch point SP and switchback point RSP in 0 1 C 0 18 F increments Minimum difference between SP and RSP 0 5 C 0 8 F Analog ou...

Page 34: ...he event of transient overvoltage up to 1 kV according to EN 61000 4 5 If the supply voltage is exceeded the specified characteristics are no longer guaranteed Behavior in the event of undervoltage If the supply voltage falls below the minimum value the device switches off in a defined manner status is the same as for not supplied with power switch open The device may be powered only by a power su...

Page 35: ...ng altitude Up to 4000 m 13123 36 ft above sea level 11 5 4 Degree of protection IP65 M16 x 1 5 or NPT valve connector IP66 M12 x 1 connector 11 5 5 Shock resistance 50 g as per DIN IEC 68 2 27 11 ms 11 5 6 Vibration resistance 20 g as per DIN IEC 68 2 6 10 2000 Hz 4 g as per marine approval 11 5 7 Electromagnetic compatibility EMC CE conformity Electromagnetic compatibility in accordance with all...

Page 36: ...ns depending on process connection and ambient temperature No restriction with compression fitting see Accessories order no 51004751 51004753 and extension neck length min 20 mm 0 79 in with process connection Max ambient temperature Max process temperature up to 25 C 77 F No restrictions up to 40 C 104 F 135 C 275 F up to 60 C 140 F 120 C 248 F up to 85 C 185 F 100 C 212 F 11 6 2 Process pressure...

Page 37: ...load caused by flow wherein a safety factor of 1 9 has been applied for operation with flow Due to the increased bending stress caused by flow the maximum permitted static operating pressure is lower in the case of longer insertion lengths This calculation is based on the maximum permitted flow velocity for the respective insertion length see diagram below The maximum process pressure for the coni...

Page 38: ...flow velocity A Water B Air L Insertion length during flow v Flow velocity The permitted flow velocity is the minimum defined by the resonance velocity resonance distance 80 and stress or buckling caused by flow which would lead to failure of the thermometer tube or to the safety factor 1 9 being exceeded The calculation was performed for the specified limit operating conditions of 200 C 392 F and...

Page 39: ... 14 0 55 35 1 38 L 14 0 55 35 1 38 38 7 1 52 24 0 95 38 7 1 52 24 0 95 6 0 24 6 0 24 6 0 24 1 2 3 A0023233 All dimensions in mm in 1 Temperature switch with extension neck and M12x1 connector according to IEC 60947 5 2 2 Temperature switch hygiene version with extension neck and M12x1 connector according to IEC 60947 5 2 3 Valve connector M16x1 5 or NPT as per DIN 43650A ISO 4400 L Insertion lengt...

Page 40: ... Thread length L1 Screw in length L2 A Without process connection Suitable welding bosses and compression fittings 29 B Threaded process connection ANSI NPT 1 AF14 ANSI NPT 1 AF27 14 3 mm 0 56 in 19 mm 0 75 in 5 8 mm 0 23 in 8 1 mm 0 32 in C Threaded process connection inches cylindrical as per ISO 228 G 2 AF14 G 2 AF27 12 mm 0 47 in 14 mm 0 55 in 11 7 3 Hygienic design dimensions of process conne...

Page 41: ...ns hygiene version Hygiene standard DB Clamp 1 to 1 ISO 2852 or DN 25 to DN 40 DIN 32676 3 A marked and EHEDG certified combined with Combifit seal DL Clamp 2 ISO 2852 or DN 50 DIN 32676 DP Clamp 2 ISO 2852 HL APV Inline DN50 PN40 316L B bores 6 x 8 6 mm 0 34 in 2 x M8 thread With 3 A symbol and EHEDG certification LB Varivent 1 F DN25 32 PN 40 LL Varivent 1 N DN40 162 PN 40 MB Metal sealing syste...

Page 42: ...ection and sensor length 11 7 5 Materials Process connection AISI 316L Surfaces in contact with the process in hygienic version with surface quality Ra 0 76 µm 30 µin Coupling nut AISI 304 AISI 316L housing with surface quality Ra 0 76 µm 30 µin O ring between housing and sensor module EPDM Electrical connection M12 connector exterior AISI 316L interior polyamide PA Valve connector polyamide PA M1...

Page 43: ...The materials of the thermometer in contact with food product FCM comply with the following European regulations EC No 1935 2004 Article 3 Paragraph 1 Articles 5 and 17 on materials and articles intended to come into contact with food EC No 2023 2006 on good manufacturing practice GMP for materials and articles intended to come into contact with food EC No 10 2011 on plastic materials and articles...

Page 44: ...ntary documentation 11 9 1 Technical Information Easy Analog RNB130 TI120R Process indicator RIA452 TI113R Universal Data Manager Ecograph T TI01079R 11 9 2 Operating Instructions Thermophant T temperature switch TTR31 TTR35 BA00229R FieldCare configuration software BA027S ...

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...www addresses endress com 71509054 71509054 ...