Installation
RN22
10
Hauser
5.2
Installing the DIN rail bus connector
If using the DIN rail bus connector for the power supply, clip it onto the DIN rail
BEFORE mounting the device. Pay attention to the orientation of the module and DIN
rail bus connector when doing so: the snap-on clip should be at the bottom and the
connector piece on the left!
1.
2.
3.
A0041738
2
Installing the DIN rail bus connector 12.5 mm (0.5 in)
1. Connect two or more DIN rail bus connectors together.
2. Attach the DIN rail bus connectors to the top of the DIN rail and allow them to click
into place on the underside of the DIN rail.
3. The DIN rail devices can now be installed.
5.3
Installing a DIN rail device
The device can be installed in any position (horizontal or vertical) on the DIN rail without
lateral clearance from neighboring devices. No tools are required for installation. The use
of end brackets (type "WEW 35/1" or similar) on the DIN rail is recommended to fix the
device.
If several devices are installed side by side, it is important to ensure that the
maximum side wall temperature of 85 °C (185 °F) is not exceeded. If this cannot be
guaranteed, mount the devices at a distance from one another or ensure sufficient
cooling.
1.
2.
3.
A0041736
3
Installing on DIN rail
1. Position the top DIN rail groove at the top end of the DIN rail.
2. While holding the front of the device horizontally, lower it until you hear the locking
clip of the device click into place on the DIN rail.
3. Pull gently on the device to check if it is correctly mounted on the DIN rail.