Commissioning
Prosonic M FMU41 HART
24
Hauser
Description of options
•
Standard liq.
• For liquid applications that do not suit any of the options
• Average filter values and output damping
•
Calm surface
• For storage tanks with an immersion tube or bottom filling
• Large filtering range and output damping
→ Stable measured value, accurate measurement, slow response time
•
Turb. surface
• For storage and buffer tanks with turbulent surfaces due to free filling, mixing nozzles or
small bottom agitators
• Emphasis on filters to stabilize the input signal
→ Steady measured value, medium response time
•
Add. agitator
• For agitated surfaces due to agitators, e.g. vortex formation
• Large values are set for filters to stabilize the input signal
→ Steady measured value, medium response time
•
Fast change
• For fast changes in the level, particularly in small tanks
• Small values are set for the filters
→ Fast response time
→ Possibly unstable measured value
•
Standard solid
• For bulk solids applications that do not suit any of the options
• Average filter values and output damping
•
Solid dusty
• For dusty bulk solids
• The filters are set in such a way that even relatively weak wanted signals are detected
•
Conveyor belt
• For bulk solids with rapid changes in the level, e.g. conveyor belts
• Low values are set for the filters.
→ Fast response time, possibly unstable measured value
•
Test: no filter
For service and diagnostics only
All the filters are switched off.