Proline Prosonic Flow 90
4 Wiring
Hauser
41
Flowrate measuring sensors U (clamp-on)
The flowrate measuring sensors U fulfill all the requirements for IP 54 degree of protection.
Compliance with the following points is mandatory following installation in the field or servicing,
in order to ensure that IP 54 protection is maintained:
• Only use cables supplied by Hauser with the corresponding sensor connectors.
• The BNC cable connectors (1) must be clean, dry and undamaged.
• Insert the BNC cable connectors (1), do not cant and then tighten them to the stop.
A0001140
Fig. 40:
Installation instructions for IP 54 degree of protection for BNC sensor connectors
4.5
Connection check
Perform the following checks after completing electrical installation of the measuring device:
Device condition and specifications
Notes
Are cables or the device damaged (visual inspection)?
−
Electrical connection
Notes
Does the supply voltage match the specifications on the nameplate?
85...260 V AC (45...65 Hz)
20...55 V AC (45...65 Hz)
16...62 V DC
Do the cables comply with the specifications?
Do the cables have adequate strain relief?
−
Cables correctly segregated by type?
Without loops and crossovers?
−
Are the power supply and sensor cables correctly connected?
See the wiring diagram inside
the cover of the terminal com-
partment
Are all screw terminals firmly tightened?
−
Have the measures for grounding/potential equalisation been correctly
implemented?
Are all cable entries installed, firmly tightened and correctly sealed?
Are all housing covers installed and firmly tightened?
−
1
Summary of Contents for Prosonic Flow 90
Page 4: ...Brief operating instructions Proline Prosonic Flow 90 4 Endress Hauser...
Page 42: ...4 Wiring Proline Prosonic Flow 90 42 Endress Hauser...
Page 62: ...5 Operation Proline Prosonic Flow 90 62 Endress Hauser...
Page 74: ...7 Maintenance Proline Prosonic Flow 90 74 Endress Hauser...
Page 78: ...8 Accessories Proline Prosonic Flow 90 78 Endress Hauser...
Page 94: ...9 Trouble shooting Proline Prosonic Flow 90 94 Endress Hauser...
Page 108: ...10 Technical data Proline Prosonic Flow 90 108 Endress Hauser...
Page 112: ...Index Proline Prosonic Flow 90 112 Endress Hauser...
Page 114: ...www endress com worldwide BA068D 06 en 11 04 50099981 FM SGLM6 0...