Commissioning
Proline t-mass 65 PROFIBUS DP/PA
62
Hauser
!
Note!
The device can’t calculate negative flow portions.
7.
Select the operating mode:
Select the operating mode (GSD file) which should be used for cyclic data transmission
with the PROFIBUS Master.
COMMUNICATION
SELECTION GSD
Selection of one of the following options:
– MANUFACT. SPEC. (factory setting): the complete device functionality is available.
– PROFILE-GSD: The device is operated in the PROFIBUS Profile mode.
!
Note!
For PROFIBUS network configuration, make sure that the right device master file (GSD
file) of the measuring device is used for the selected operating mode
8.
Configuration of cyclic data transmission in the PROFIBUS master:
A detailed description of the cyclic data transmission can be found at
PROFIBUS DP
7.5
PROFIBUS DP/PA system integration
7.5.1
Device master file (GSD file)
For PROFIBUS network configuration, the device master file (GSD file) is needed for every
bus participant (PROFIBUS slave). The GSD file contains a description of the properties of a
PROFIBUS device, such as supported data transmission rate and number of input and output
data. Before configuration takes place, a decision should be made as to which GSD file should
be used to operate the measuring device in the PROFIBUS DP Master (class 1) system.
The measuring device supports the following GSD files:
• t-mass GSD file (manufacturer-specific GSD file, complete device functionality)
• PROFIBUS Profile GSD file:
Below you will find a detailed description of the GSD files supported.
GSD file (manufacturer-specific GSD file, complete device functionality)
Use this GSD file to access the complete functionality of the measuring device. In this way,
device-specific measured variables and functions are thus completely available in the PRO-
FIBUS master system. An overview of the modules available (input and output data) is con-
tained on
GSD file with standard or extended format
The GSD file with either the standard or the extended format must be used depending on the
PROFIBUS Master used. When installing the GSD file, the GSD file with the extended format
(EH3
x
15xx.gsd) should always be used first.
However, if the installation or the configuration of the measuring device fails with this for-
mat, then use the standard GSD (EH3_15xx.gsd). This differentiation is the result of differ-
ent implementation of the GSD formats in the master systems.
Pay attention to the specifications of the configuration software.