Proline t-mass 65 PROFIBUS DP/PA
Operation
Hauser
45
6.6.2
Configuring the device address
The address must always be configured for a PROFIBUS DP/PA device. Valid device
addresses are in the range from 1 to 126. Each address can only be assigned once in a PRO-
FIBUS DP/PA network. If an address is not configured correctly, the device is not recognized
by the master. All measuring devices are delivered from the factory with the address 126
and software addressing.
Addressing via local operation or operating program
Addressing takes place in the FIELDBUS ADDRESS function
see "Description of Device
Functions" manual.
Addressing via miniature switches
#
Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Switch off the power
supply before you remove the cover of the electronics compartment.
1.
Loosen Allen screw (3 mm) of the securing clamp.
2.
Unscrew cover of the electronics compartment from the transmitter housing.
3.
Remove the local display (if present). To do so, loosen the set screws of the display mod-
ule.
4.
Set the position of the miniature switches on the I/O board using a sharp pointed object.
5.
Installation is the reverse of the removal procedure.
A0002821
Fig. 31:
Addressing with the aid of miniature switches on the I/O board
a
Miniature switches for setting the device address (illustrated: 1 + 16 + 32 = device address 49)
b
Miniature switches for the address mode (method of addressing):
OFF = software addressing via local operation or operating program (factory setting)
ON = hardware addressing via miniature switches
c
Miniature switches not assigned
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
16
1
3
32
2
4
6
4
3
4
1
2
b
O
FF
ON
1
1
2
2
4
3
8
4
a
O
FF
ON
c
Summary of Contents for Proline t-mass 65 PROFIBUS DA
Page 127: ...www addresses endress com ...