Description of Device Functions

Proline t-mass 65
MODBUS RS485

Thermal Mass Flow Measuring System

Summary of Contents for Proline t-mass 65 MODBUS RS485

Page 1: ...BA00116D 06 EN 13 10 71123867 Valid as of version V 3 06 XX Device software Description of Device Functions Proline t mass 65 MODBUS RS485 Thermal Mass Flow Measuring System...

Page 2: ......

Page 3: ...NG VALUES 7 4 SYSTEM UNITS 8 5 QUICK SETUP 11 6 OPERATION 23 7 USER INTERFACE 25 8 TOTALIZER 1 2 28 9 HANDLING TOTALIZER 30 10 STATUS INPUT 31 11 COMMUNICATION 33 12 PROCESS PARAMETER 35 13 GAS 39 14...

Page 4: ...igned to each group You select a group in order to access the individual functions for operating and configuring the measuring device An overview of all the groups available is provided in the table o...

Page 5: ...R USER INTERFACE 25 ASSIGN LINE 1 ASSIGN LINE 2 100 VALUE LINE 1 100 VALUE LINE 2 FORMAT DISPLAY DAMPING CONTRAST LCD BACKLIGHT TEST DISPLAY TOTALIZER 1 2 28 ASSIGN TOTALIZER SUM OVERFLOW UNIT TOTALIZ...

Page 6: ...TERNAL HEIGHT INTERNAL WIDTH MOUNTING MOUNTING SET LENGTH INSERTION DEPTH ZERO POINT FLOW CONDITIONER SUPERVISION 51 ACTUAL SYSTEM CONDITION PREVIOUS SYSTEM CONDITION ALARM DELAY SYSTEM RESET OPERATIO...

Page 7: ...ected volume flow appears on the display The corrected volume flow is calculated from the measured mass flow and the reference density of the gas Display 5 digit floating point number including unit e...

Page 8: ...FLOW Description For selecting the unit required and displayed for the corrected volume flow The unit you select here is also valid for Low flow cut off The following time units can be selected s sec...

Page 9: ...al time unit Options US unit 26 tons 27 30 kBtu time unit 31 34 MBtu time unit 35 38 GBtu time unit Factory setting kW or kBtu h country dependent 55 MODBUS register Data type Access 2132 Integer read...

Page 10: ...ing kg m or lb ft country dependent 55 MODBUS register Data type Access 2107 Integer read write UNIT LENGTH Prerequisite This function is only available for the insertion sensor t mass 65I Description...

Page 11: ...te This function is only available for insertion sensors t mass 65I Description Use this function to start the application specific setup to calculate the insertion depth for the insertion sensor For...

Page 12: ...nt parameters can be saved to the T DAT as a backup If the transmitter is replaced for some reason the data from the T DAT can be loaded into the new transmitter EEPROM Options 0 CANCEL 1 SAVE from th...

Page 13: ...s Heat Flow Unit Heat Flow Unit Quantity Heat Pressure Unit Pressure Totalizer 1 Totalizer 2 Yes No Configure another totalizer Unit Totalizer 1 Assign Totalizer 1 Assign Gas Group Unit Calorific Valu...

Page 14: ...s required n Only units not yet configured in the current setup are available for selection in each cycle o The YES option remains visible until all the units have been configured NO is the only optio...

Page 15: ...Setup A0005503 en Fig 2 Quick Setup communication E E Esc E XXX XXX XX Quick Setup HOME POSITION QS Communication Fieldbus Address Baudrate Transmission Mode Parity Byte Order Delay Telegram Reply Set...

Page 16: ...THICKNESS and OUTER DIAMETER The function INTERNAL DIAMETER displays the calculated internal diameter and is read only RECTANGULAR Enter the INTERNAL HEIGHT INTERNAL WIDTH and WALL THICKNESS of the du...

Page 17: ...med as one single gas or one gas mixture of up to 8 components A single gas can be selected from a list of standard gases or setup for other suitable types of gases such as Ozone using manual correcti...

Page 18: ...from the choose list enter the MOLE for each GAS TYPE only if NUMBER OF GASES is 2 and more The error message CHECK VALUES appears if the total mixture does not equal 100 Go back and check the mixture...

Page 19: ...essures to absolute pressure If a pressure compensating input is being used then the input signal value overrides the manually programmed value The pressure input value applies to both gas groups i e...

Page 20: ...UP 2 Note If only one gas group is used then leave mode 2 as default settings The units of measure are selected in the SYSTEM UNITS section 8 Auto Gross The gross heating value or higher heating value...

Page 21: ...bon Monoxide CO 10 1 4 34 10 1 4 34 Hydrogen Sulphide H2S 15 2 6 54 19 49 8 38 Methane CH4 50 02 21 51 55 52 23 87 Ethane C2H6 47 5 20 43 51 93 22 33 Propane C3H8 46 32 19 92 50 32 21 64 Butane C4H10...

Page 22: ...or information on installing and removing the T DAT see Operating Instructions BA00115D 06 a0001221 en Fig 3 Data backup transmission with T DAT SAVE LOAD function Information on the LOAD and SAVE opt...

Page 23: ...ou can enable programming by entering the private code factory setting 65 see DEFINE PRIVATE CODE function 23 The programming levels are disabled if you do not press the operating elements within 60 s...

Page 24: ...nnot be modified 1 ACCESS CUSTOMER parameters can be modified MODBUS register Data type Access 2512 Integer read write ACCESS CODE COUNTER Description The number of times the private and service code...

Page 25: ...ration Options 0 OFF 1 MASS FLOW 2 MASS FLOW IN 3 MASS FLOW BARGRAPH IN 4 TEMPERATURE 5 TOTALIZER 1 6 TOTALIZER 2 9 TAG NAME 10 OPERATING SYSTEM CONDITIONS 11 CORRECTED VOLUME FLOW 12 CORRECTED VOLUME...

Page 26: ...r the decimal point as computed by the measuring device cannot always be displayed depending on this setting and the engineering unit In these instances an arrow appears on the display between the mea...

Page 27: ...ility of the local display and its pixels Test sequence 1 Start the test by selecting ON 2 All pixels of the main line and additional line are darkened for minimum 0 75 seconds 3 The main line and add...

Page 28: ...aggregated since measuring commenced appears on the display Total flow is represented by a floating point number consisting of max 7 digits Higher numerical values 9 999 999 can be viewed as overflows...

Page 29: ...user 29 RESET TOTALIZER Description Resets the sum and overflow in the totalizer selected Options 0 NO 1 YES Factory setting NO MODBUS register TOTALIZER 1 TOTALIZER 2 Data type Access 2608 2808 Integ...

Page 30: ...1 YES Factory setting NO MODBUS register Data type Access 2609 Integer read write FAILSAFE MODE Description For selecting the behavior of the totalizer in an alarm condition Options 0 STOP The totaliz...

Page 31: ...ing OFF MODBUS register Data type Access 4301 Integer read write ACTIVE LEVEL Description Use this function to define whether the assigned switching function see ASSIGN STATUS INPUT function is trigge...

Page 32: ...ata type Access 4306 Integer read write VALUE SIMULATION STATUS INPUT Prerequisite This function is only available if ON was selected in the SIMULATION STATUS INPUT function 32 Description Use this fu...

Page 33: ...e this function for selecting the baud rate Options 0 1200 BAUD 1 2400 BAUD 2 4800 BAUD 3 9600 BAUD 4 19200 BAUD 5 38400 BAUD 6 57600 BAUD 7 115200 BAUD Factory setting 19200 BAUD MODBUS register Data...

Page 34: ...vated and deactivated by means of a jumper on the I O module see Operating Instructions BA00115D 06 Display 0 OFF write access via MODBUS possible 1 ON write access via MODBUS blocked Factory setting...

Page 35: ...nt number Factory setting 1 0130 bar a or 14 692 psi a country dependent 55 MODBUS register Data type Access 5270 Float read write PROCESS PRESSURE Description Use this function to display the pressur...

Page 36: ...MASS 8 or UNIT CALORIFIC VALUE CORRECTED VOLUME 9 Display 5 digit floating point number MODBUS register Data type Access 5272 Float read GROSS CALORIFIC VALUE Prerequisite This function is only avail...

Page 37: ...ing point number Factory setting 1 of full scale value MODBUS register Data type Access 5138 Float read write OFF VALUE LOW FLOW CUT OFF Description Use this function to enter the off value for low fl...

Page 38: ...function RESET restores the factory calibration If the status input is appropriately configured the zero point adjustment can also be activated by using the status input see the ASSIGN STATUS INPUT fu...

Page 39: ...orresponding Mole can be entered in any order within the mixture A gas constituent may have a value of 0 0 Mole within the mixture The option NOT USED is only a place holder for functions GAS TYPE 1 a...

Page 40: ...t are used in the gas group User input 1 to 8 Factory setting 1 MODBUS register Data type Access 9717 Float read write GAS TYPE 1 Description Use this function to select gas type 1 Options 0 AIR 1 AMM...

Page 41: ...the specified process conditions The correction factor is determined by the factory If the gas or process conditions change from the initial setting then the correction factor value will also need upd...

Page 42: ...number of functions available here is dependent upon the setting in the function NUMBER OF GASES 40 Description Use this function to enter the Mole of the GAS TYPE 2 to 8 User input 000 00 to 100 00 F...

Page 43: ...measurement 1 CANCEL The entered parameters are saved in the gas group but they are not used for flow measurement The gas group can be activated at a later time by returning to the group checking the...

Page 44: ...a user specific calorific value Input display 5 digit floating point number Factory setting 0 0 The corresponding unit is taken from the UNIT CALORIFIC VALUE MASS 8 or UNIT CALORIFIC VALUE CORRECTED V...

Page 45: ...escription Use this function to enter the reference combustion temperature of the gas This function is used to calculate the calorific value of the gas The unit is taken from the function UNIT TEMPERA...

Page 46: ...put is appropriately configured the positive zero return function can also be activated by using the status input ASSIGN STATUS INPUT 31 Options 0 OFF 1 ON signal output is set to zero flow value temp...

Page 47: ...sors t mass 65I Description Use this function to select the type of pipe Options 0 CIRCULAR 1 RECTANGULAR Factory setting CIRCULAR MODBUS register Data type Access 9603 Integer read write PIPE STANDAR...

Page 48: ...YPE 47 and OTHER was selected in the function PIPE STANDARD 47 Description Use this function to enter a value for the outer diameter if the required pipe standard was not available in the function PIP...

Page 49: ...er Data type Access 9606 Float read write INTERNAL WIDTH Prerequisite This function is only available for insertion sensors t mass 65I This function is only available if RECTANGULAR was selected in th...

Page 50: ...nction UNIT LENGTH 10 For more information on insertion depth calculation please refer to the Operating Instructions BA00115D 06 Display 5 digit floating point number MODBUS register Data type Access...

Page 51: ...could affect the safety requirements of the process If fault and notice messages are not be suppressed than a value of 0 seconds must be entered here User input 0 to 100 s in steps of one second Facto...

Page 52: ...y be used for measuring to a certain extent while the simulation is in progress The setting is not saved if the power supply fails Options 0 OFF 1 MASS FLOW 2 CORRECTED VOLUME FLOW 3 TEMPERATURE 4 HEA...

Page 53: ...NSDUCER SERIAL NUMBER Description The serial number of the transducer appears on the display MODBUS register Data type Access 7461 String 16 read SOFTWARE REVISION NUMBER S DAT Description Use this fu...

Page 54: ...SOFTWARE REVISION NUMBER AMPLIFIER Description Use this function to view the software revision number of the amplifier board MODBUS register Data type Access 7039 String 16 read SOFTWARE REVISION NUMB...

Page 55: ...Norway Norwegian Denmark English Poland Polish England English Portugal Portuguese Finland Finnish Sweden Swedish France French Switzerland German Germany German Singapore English Hungary English Spai...

Page 56: ...1000 3200 00 320000 100 0 1500 7200 00 720000 100 0 Unit Unit Temperature C Length mm Density kg m Pressure bar a Reference density kg m Reference Pressure bar a Calorific Value Mass MJ kg Calorific V...

Page 57: ...20 1220 2 00 2 20 02 2002 20 00 3 44 66 4466 20 00 4 82 50 8250 20 00 Nominal diameter Low flow cut off Full scale value Pulse value mm lb hr lb hr lb p 3 44 66 4466 20 00 4 82 50 8250 20 00 6 165 00...

Page 58: ...e t mass 65 MODBUS RS485 58 Endress Hauser 21 3 3 Unit totalizer 1 and 2 28 21 3 4 Other Units Unit Unit Mass flow lb Corrected volume flow Sm Heat flow kBtu Unit Ref combustion temp F 45 Pipe standar...

Page 59: ...50 FLOW DAMPING fct 46 FORMAT fct 26 G Gas pressure 19 Gas programming 17 GAS TYPE 1 fct 40 GAS TYPE 2 to 8 fct 42 GAS function group 39 GROSS CALORIFIC VALUE fct 36 H HANDLING TOTALIZER function grou...

Page 60: ...ct 53 SIMULATION FAILSAFE MODE fct 52 SIMULATION MEASURAND fct 52 SIMULATION STATUS INPUT fct 32 SIMULATION SYSTEM function group 52 SOFTWARE REVISION NUMBER AMPLIFIER fct 54 SOFTWARE REVISION NUMBER...