Proline Prosonic Flow 91
Installation
Hauser
33
3.14
Post-connection check
Perform the following checks after completing electrical installation of the measuring device:
Device condition and specifications
Notes
Are cables or the device damaged (visual inspection)?
-
Electrical connection
Notes
Does the supply voltage match the specifications on the nameplate?
• 85 to 250 V AC (50 to 60 Hz)
• 20 to 28 V AC (50 to 60 Hz),
10 to 40 V DC
Do the cables comply with the specifications?
Do the cables have adequate strain relief?
-
Is the cable type route completely isolated?
Without loops and crossovers?
-
Are the power supply and signal cables correctly connected?
See the wiring diagram inside
the cover of the terminal
compartment
Are all screw terminals firmly tightened?
-
Have the measures for grounding/potential equalization been correctly
implemented?
Are all cable entries installed, firmly tightened and correctly sealed?
Are all housing covers installed and firmly tightened?
-