Parameter overview with brief description
Parameters
Prerequisite
Description
Display
Totalizer value 1-3
One of the following options is selected
in the
Assign process variable
parameter of the
Totalizer 1-3
submenu:
• Mass flow
• Volume flow
• Corrected volume flow
Displays the current
totalizer counter value.
Floating point number
with sign
Totalizer overflow 1-3
One of the following options is selected
in the
Assign process variable
parameter of the
Totalizer 1-3
submenu:
• Mass flow
• Volume flow
• Corrected volume flow
Displays the current
totalizer overflow.
Integer
11.4.3 Output values
The
Output values
submenu contains all the parameters needed to display the current measured
values for every output.
Navigation path
"Diagnostics" menu
®
Measured values
®
Output values
Structure of the submenu
Output values
®
Output current 1
Measured current 1
Terminal voltage 1
Output current 2
Pulse output
Output frequency
Switch status
Parameter overview with brief description
Parameters
Prerequisite
Description
Display
Output current 1-2
-
Displays the current value
currently calculated for
the current output.
3.59 to 22.5 mA
Measured current 1
-
Displays the current value
currently measured for
the current output.
3.59 to 22.5 mA
Terminal voltage 1
-
Displays the current
terminal voltage that is
applied at the current
output.
-