Proline Promass E TB2 HART
Technical data
Hauser
99
Protocol-specific data
• For information on the device description files (
• For information on the HART device variables and measured values
• For information on the HART commands
18.5
Power supply
Terminal assignment
Order version
Output
Terminal numbers
3 (+)
4 (-)
1 (+)
2 (-)
8E2B**-**
C
********
4-20 mA
4-20 mA HART
Supply voltage
Order version,
output
U
S
*
(supply voltage)
I
max
(output current)
8E2B**-**
C
********
18 to 30 V DC
22.0 mA
*
Supply voltage range without load. For information on the supply voltage with a load (
Power consumption
• Operation with current output 1: 65 to 660 mW
• Operation with current output 1 and 2: 130 to 1
320 mW
Power supply failure
• Totalizers stop at the last value measured.
• Configuration is retained in the HistoROM.
• Error messages (incl. total operated hours) are stored.
Electrical connection
Load
Potential equalization
No special measures for potential equalization are required.
Terminals
Plug-in spring terminals for wire cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
Cable entries
• Cable gland: M20 × 1.5 with cable
Æ
6 to 12 mm (0.24 to 0.47 in)
• Thread for cable entry: ½" NPT, G ½"
Cable specification
• Permitted temperature range: –40
°
C (–40
°
F) to
³
80
°
C (176
°
F); at least ambient temperature
+ 20 K
• A normal device cable suffices if only the analog signal is used.
• A shielded cable is recommended if using the HART protocol. Observe grounding concept of the
plant.