Supply voltage
85 to 260 V AC, 45 to 65 Hz
20 to 55 V AC, 45 to 65 Hz
16 to 62 V DC
Switching on the power
supply in custody transfer
mode
If the device is started in custody transfer mode, for example also after a power outage, system error No. 271
"POWER BRK. DOWN" flashes on the local display. The fault message can be acknowledged or reset using the
"Enter" key or by means of the status input configured accordingly.
Cable entries
Power-supply and signal cables (inputs/outputs):
• Cable entry M20 × 1.5 (8 to 12 mm)
• Thread for cable entries, ½" NPT, G ½"
Connecting cable for remote version:
• Cable entry M20 × 1.5 (8 to 12 mm)
• Thread for cable entries, ½" NPT, G ½"
Remote version cable
specifications
• 6 × 0.38 mm
2
PVC cable with common shield and individually shielded cores
• Conductor resistance:
≤
50
Ω
/km
• Capacitance: core/shield:
≤
420 pF/m
• Cable length: max. 20 m
• Operating temperature: max. +105 °C
Operation in zones of severe electrical interference:
The measuring device complies with the general safety requirements in accordance with EN 61010-1,
the EMC requirements of ICE/EN 61326, and NAMUR recommendation NE 21/43.
Power consumption
AC: <15 VA (including sensor)
DC: <15 W (including sensor)
Switch-on current
• Max. 13.5 A (< 50 ms) at 24 V DC
• Max. 3 A (< 5 ms) at 260 V AC
Power supply failure
Lasting min. 1 power cycle:
• EEPROM or T-DAT save measuring system data if the power supply fails.
• S-DAT: exchangeable data storage chip with sensor specific data
(nominal diameter, serial number, calibration factor, zero point, etc.)
• See Note on Page 11 "Switching on the power supply in custody transfer mode"
Potential equalisation
No special measures for potential equalization are required. For instruments for use in hazardous areas, observe
the corresponding guidelines in the specific Ex documentation.