Proline Promag L 400 HART
Commissioning
Hauser
69
10.4.2 Configuring the current output
The
Current output
wizard guides you systematically through all parameters that have to be set
for configuring the specific current output.
Navigation path
"Setup" menu
®
Current output
Sequence of the wizard
Volume flow
Assign curr.
Mass flow
Conductivity
Volume flow unit
4...20 mA NAMUR
4...20 mA US
4...20 mA
Fixed current
0/4 mA value
20 mA value
Failure mode
Defined value
Min.
…
Failure current
End of wizard
Off
Mass flow unit
Conductiv. unit
Density unit
Fixed density
Current span
0...20 mA
A0017434-EN
å
22
Graphic of "Current output" wizard in the "Setup" menu
Parameter overview with brief description
Parameters
Description
Selection/
User entry
Factory setting
Assign current output
Select process variable for
current output.
• Off
• Volume flow
• Conductivity
• Mass flow
Volume flow