background image

Electrical connection

Proline Promag H 100

32

Hauser

Potential equalization via ground electrodes on process connection

2

1

3

4

  A0017293

1

Allen screw (process connection)

2

Integrated ground electrodes

3

O-ring seal

4

Sensor

7.3 

Hardware settings

7.3.1 

Setting the device address

EtherNet/IP

The IP address of the measuring device can be configured for the network via DIP switches.

Addressing data

IP address and configuration options

1st octet

2nd octet

3rd octet

4th octet

192.

168.

1.

XXX

Can only be configured via software addressing

Can be configured via
software addressing
and hardware
addressing

Summary of Contents for Proline Promag H 100 EtherNet/IP

Page 1: ...hese Instructions are Brief Operating Instructions they do not replace the Operating Instructions included in the scope of supply For detailed information refer to the Operating Instructions and other...

Page 2: ...ons 14 6 2 Mounting the measuring device 19 6 3 Post installation check 23 7 Electrical connection 24 7 1 Connection conditions 24 7 2 Connecting the measuring device 28 7 3 Hardware settings 32 7 4 E...

Page 3: ...rical symbols Symbol Meaning A0011197 Direct current A terminal to which DC voltage is applied or through which direct current flows A0011198 Alternating current A terminal to which alternating voltag...

Page 4: ...at are preferred A0011184 Forbidden Indicates procedures processes or actions that are forbidden A0011193 Tip Indicates additional information A0011194 Reference to documentation Refers to the corresp...

Page 5: ...ending on the version ordered the measuring device can also measure potentially explosive flammable poisonous and oxidizing media Measuring devices for use in hazardous areas in hygienic applications...

Page 6: ...of the electronic components Hot process fluids passing through the measuring device will further increase the surface temperature of the housing The surface of the sensor in particular can reach tem...

Page 7: ...ity We only provide a warranty if the device is installed and used as described in the Operating Instructions The device is equipped with security mechanisms to protect it against any inadvertent chan...

Page 8: ...duct description 3 1 Product design 3 1 1 Device version with HART Modbus RS485 and PROFIBUS DP communication types 2 3 4 1 A0017609 1 Important components of a measuring device 1 Transmitter housing...

Page 9: ...ser 9 3 1 2 Device version with EtherNet IP communication type 2 3 4 5 1 A0017257 2 Important components of a measuring device 1 Transmitter housing cover 2 I O electronics module for EtherNet IP 3 Ma...

Page 10: ...ance and product identification Proline Promag H 100 10 Endress Hauser 4 Incoming acceptance and product identification 4 1 Incoming acceptance A0015502 1 2 1 2 A0013843 A0013695 A0015502 A0013698 A00...

Page 11: ...numbers from nameplates in W M Device Viewer www endress com deviceviewer All information about the measuring device is displayed For an overview of the scope of the Technical Documentation provided r...

Page 12: ...WARNING Center of gravity of the measuring device is higher than the suspension points of the webbing slings Risk of injury if the measuring device slips Secure the measuring device from rotating or...

Page 13: ...Proline Promag H 100 Storage and transport Endress Hauser 13 A0015604 A0015605...

Page 14: ...Mounting location h 2 DN h A0017061 Installation in down pipes Install a siphon or a vent valve downstream of the sensor in down pipes whose length h 5 m 16 4 ft This precaution is to avoid low pressu...

Page 15: ...ps you to install the sensor according to the flow direction An optimum orientation position helps avoid gas and air accumulations and deposits in the measuring tube Vertical This is the optimum orien...

Page 16: ...et and outlet runs 5 DN 2 DN A0016275 For the dimensions and installation lengths of the device see the Technical Information document Mechanical construction section 6 1 2 Requirements from environme...

Page 17: ...itions Temperature tables SI units Ta C T6 85 C T5 100 C T4 135 C T3 200 C T2 300 C T1 450 C 30 50 95 130 150 150 150 50 95 130 150 150 150 60 95 110 110 110 110 US units Ta F T6 185 F T5 212 F T4 275...

Page 18: ...omag H 100 18 Endress Hauser Vibrations L A0016266 6 Measures to prevent vibration of the device L 10 m 33 ft Adapters 100 10 0 5 d D mbar 0 6 0 7 0 8 0 9 1 m s 2 m s 3 m s 4 m s 5 m s 6 m s 7 m s 8 m...

Page 19: ...s sealing Ensure that the inside diameters of the gaskets are greater than or equal to that of the process connections and piping Ensure that the gaskets are clean and undamaged Install the gaskets co...

Page 20: ...Welding the sensor into the pipe welding connections WARNING Risk of destroying the electronics Make sure that the welding system is not grounded via the sensor or transmitter 1 Tack weld the sensor t...

Page 21: ...nt seals can be ordered as an accessory Mounting grounding rings DN 2 to 25 1 12 to 1 Pay attention to the information on potential equalization 29 In the case of plastic process connections e g flang...

Page 22: ...from the sensor 4 2 Remove the plastic disk 3 along with the two O ring seals 2 from the process connection 3 Place the first O ring seal 2 back into the groove of the process connection 4 Fit the met...

Page 23: ...Information document on the CD ROM provided Ambient temperature Measuring range Has the correct orientation for the sensor been selected 15 According to sensor type According to medium temperature Acc...

Page 24: ...ing cables provided by the customer must fulfill the following requirements Electrical safety In accordance with applicable federal national regulations Permitted temperature range 40 C 40 F to 80 C 1...

Page 25: ...pacitance 30 pF m Wire cross section 0 34 mm2 22 AWG Cable type Twisted pairs Loop resistance 110 km Signal damping Max 9 dB over the entire length of the cable cross section Shielding Copper braided...

Page 26: ...th pulse frequency switch output 4 20 mA HART with pulse frequency switch output on the device side 3 2 4 1 5 A0016810 Pin Assignment Coding Plug socket 1 4 20 mA HART active A Socket 2 4 20 mA HART a...

Page 27: ...on protection Personal protection equipment National installation regulations and guidelines Observe cable specification 24 Keep the stripped and twisted lengths of cable shield to the ground terminal...

Page 28: ...mitation of electrical safety due to incorrect connection For use in potentially explosive atmospheres observe the information in the device specific Ex documentation 7 2 1 Connecting the transmitter...

Page 29: ...plug for supply voltage Connect the cable in accordance with the terminal assignment or the device plug pin assignment 26 7 2 2 Ensuring potential equalization CAUTION Electrode damage can result in...

Page 30: ...the sensor through the electrochemical decomposition of the electrodes When using ground rings note the following points Depending on the option ordered plastic disks may be installed at the process c...

Page 31: ...g H 100 Electrical connection Endress Hauser 31 Potential equalization via additional ground ring 1 3 2 4 2 A0002651 1 Allen screw process connection 2 O ring seals 3 Plastic washer spacer or ground r...

Page 32: ...odes 3 O ring seal 4 Sensor 7 3 Hardware settings 7 3 1 Setting the device address EtherNet IP The IP address of the measuring device can be configured for the network via DIP switches Addressing data...

Page 33: ...s setting last octet A0017913 1 Set the desired IP address using the corresponding DIP switches on the I O electronics module Hardware addressing with the configured IP address is enabled after 10 s 2...

Page 34: ...IP address 7 3 2 Enabling the terminating resistor PROFIBUS DP To avoid incorrect communication transmission caused by impedance mismatch terminate the PROFIBUS DP cable correctly at the start and en...

Page 35: ...isation Bus termination Bus polarisation Not used 4 1 2 3 A0021274 12 Termination using DIP switches on the I O electronics module for baud rates 1 5 MBaud Modbus RS485 To avoid incorrect communicatio...

Page 36: ...measuring device fulfills all the requirements for the IP66 67 degree of protection Type 4X enclosure To guarantee IP66 67 degree of protection Type 4X enclosure carry out the following steps after th...

Page 37: ...tch the specifications on the transmitter nameplate For device version with Modbus RS485 intrinsically safe does the supply voltage match the specifications on the nameplate of the Safety Barrier Prom...

Page 38: ...y The individual parts of the operating menu are assigned to certain user roles Each user role corresponds to typical tasks within the device lifecycle For detailed information about the operating phi...

Page 39: ...ructure starts in the Web browser 8 2 3 Establishing a connection Configuring the Internet protocol of the computer The following information refers to the default Ethernet settings of the device IP a...

Page 40: ...ce 1 2 OK A0017362 1 Device tag 46 2 Picture of device 8 2 4 Logging on Access code 0000 factory setting can be changed by customer 47 8 2 5 User interface 2 4 6 5 1 3 2 4 6 5 1 3 2 4 6 5 1 3 2 4 6 5...

Page 41: ...file Export parameter settings csv file create documentation of the measuring point Export the Heartbeat verification log PDF file only available with the Heartbeat Verification application package U...

Page 42: ...rface CDI RJ45 1 2 3 A0016926 14 Connection for the order code for Output option B 4 20 mA HART pulse frequency switch output 1 Service interface CDI RJ45 of the measuring device with access to the in...

Page 43: ...FieldCare operating tool with COM DTM CDI Communication TCP IP 3 Standard Ethernet connecting cable with RJ45 plug 1 2 3 A0016940 16 Connection for order code for Output option N EtherNet IP 1 Servic...

Page 44: ...COM DTM CDI Communication TCP IP 5 Ethernet switch 8 3 4 Establishing a connection For device version with EtherNet IP communication type Via service interface CDI RJ45 and FieldCare operating tool 1...

Page 45: ...elect the desired device from the list and press OK to confirm 6 Establish the online connection to the device For details see Operating Instructions BA00027S and BA00059S 9 System integration For sys...

Page 46: ...ion then the first three octets of the software address are retained If the IP address of the device is not known the device address currently configured can be read out Operating Instructions for the...

Page 47: ...h the customer specific access code access to the measuring device via the Web browser is protected as are the parameters for the measuring device configuration Navigation Setup menu Advanced setup Ad...

Page 48: ...nal temperature Reference density All parameters for configuring the totalizer The parameter values are now read only and cannot be edited any more Via service interface CDI Via HART protocol Via Modb...

Page 49: ...15 For device version with PROFIBUS DP communication type OFF ON 1 2 3 4 5 6 7 8 9 10 1 2 4 8 16 32 64 Write protection Not used PROFIBUS address Software addressing A0021262 Setting the write protect...

Page 50: ...ion has been established and on the home page of the web browser once the user has logged on Remedial measures are provided for each diagnostic event to ensure that problems can be rectified quickly W...

Page 51: ......

Page 52: ...www addresses endress com...

Reviews: