Description of device parameters
Proline Promag 300 Modbus RS485
110
Hauser
smaller than the value assigned for the 0/4 mA current in the
0/4 mA value
parameter
Dependency
The unit depends on the process variable selected in the
Assign curr.
parameter
Example
• Value assigned to 0/4 mA = –250 m
3
/h
• Value assigned to 20 mA = +750 m
3
/h
• Calculated current value = 8 mA (at zero flow)
If the
Forward/Reverse
option is selected in the
Measuring mode
parameter
(→ 110), different signs cannot be entered for the values of the
0/4 mA value
20 mA value
parameter (→ 109). The diagnostic message
S441 Curr.output 1 to n
is displayed.
Configuration examples
Observe the configuration examples for the
0/4 mA value
Measuring mode
Navigation
Expert → Output → Curr.output 1 to n → Measuring mode (0351–1 to n)
Prerequisite
One of the following options is selected in the
Assign curr.
• Volume flow
• Mass flow
• Correct.vol.flow
• Flow velocity
• Conductivity
• CorrConductivity
• Temperature
• Electronic temp.
One of the following options is selected in the
Current span
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Description
Use this function to select the measuring mode for the current output.
Selection
• Forward flow
• Forward/Reverse
• Rev. flow comp.
Factory setting
Forward flow
*
Visibility depends on order options or device settings