Electrical connection
LPGmass Modbus RS485
26
Hauser
7.2.1
Connecting the transmitter
1
2
A
A0030221
8
Housing versions and connection versions
A
Housing version: compact, aluminum coated
1
Cable entry for signal transmission
2
Cable entry for supply voltage
10 (0.4)
1
3 mm
A0030223
9
Device versions with connection example. Engineering unit mm (in)
1
Cable
1. Loosen the securing clamp of the housing cover.
2. Unscrew the housing cover.
3. Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4. Strip the cable and cable ends. In the case of stranded cables, also fit ferrules.
5. Connect cable in accordance with terminal assignment→ 24.
6. Firmly tighten cable glands .