Micropilot FMR51, FMR52 HART
Operating menu
Hauser
123
Additional information
The value specified in this parameter is added to the measured level (before linearization).
Tank/silo height
Navigation
Setup → Advanced setup → Level → Tank/silo height
Description
Specify total height of the tank or silo as measured from the process connection.
User entry
–999.9999 to 999.9999 m
Factory setting
Empty calibration (→ 109)
Additional information
If the parametrized measuring range (
Empty calibration (→ 109)
) differs significantly
from the tank or silo height, it is recommended to enter the tank or silo height. Example:
Continuous level monitoring in the upper third of a tank or silo.
0%
E
1
A0019867
31
'"Tank/silo height" parameter (→ 123)' for measurements in liquids
E
1
Tank/silo height (→ 123)
For tanks with conical outlet,
Tank/silo height
should not be changed as in this type
of applications
is usually
not
<< the tank or silo
height.