Liquiphant M/S with electronic insert FEL58 + Nivotester FTL325N
Hauser
43
Report for versions II to VI
System-specific data
Company
Measuring point/TAG no.
Facility
Device type/Order code
Serial no. of Liquiphant(s)
Serial no. of Nivotester
Name
Date
Signature
Operating mode, density range and version (please tick appropriate box)
Mode of operation
MIN safety
MAX safety
Density switch
Setting >0.7
Setting >0.5
Version
II
One Liquiphant at one channel (1oo1)
III
One Liquiphant (1oo1), output relay CH2 and CH3 switched in series (1oo2)
IV
Two Liquiphants (1oo2), output relay CH1, CH2 and CH3 switched in series (1oo3)
V
Three Liquiphants, evaluation e.g. by PLC (2oo3)
VI
Three Liquiphants, 1 x SIL, 2 x level control (∆s)
Commissioning or proof test report
Test sequence
A
Approach the level
Remove and immerse in a medium of similar density and viscosity
B
Simulation on Liquiphant by pressing the test button
Simulation on Nivotester by pressing the test button
C
Check the switch point under reference operating conditions
Version
Test step
Terminal II
III
IV
V
VI
Actual value
Step 1
4+5
(GOOD state)
22+23
Switch is closed
26+27
Step 2
4+5
(demand mode)
22+23
Switch is open
26+27
Step 3
4+5
(GOOD state)
22+23
Switch is closed
26+27
Conclusion
Passed
Failed
1)
Only for Liquiphant with electronic insert FEL58 + Nivotester FLT325N.
2)
For restrictions and immersion depths see, → 35
3)
Not applicable as channel is not used.
4)
Not relevant for SIL, is used for level control (∆s).