Liquiphant FTL64

Commissioning

Hauser

37

Bluetooth module VU121 (optional)

Functions

• Connection via COM interface: Bluetooth module for device diagnostics via a smartphone

app or tablet app

• Display the battery status via app when used with electronic insert FEL68 (NAMUR)

• User guidance (wizard) for SIL/WHG proof testing

• Visible in the livelist 10 s seconds after the Bluetooth search commences

• Data can be read from the Bluetooth module 60 s after the supply voltage is switched on

• Display of the current vibration frequency and the switching state of the device
The yellow LED flashes when the Bluetooth module is connected to another Bluetooth

device, e.g. cellular phone.

Heartbeat Technology

Heartbeat Technology module

Heartbeat Diagnostics

Continuously monitors and evaluates the device status and process conditions. Generates

diagnostic messages when certain events occur and provides troubleshooting measures in

accordance with NAMUR NE 107.
Heartbeat Verification

Performs a verification of the current device status upon request and generates a

Heartbeat Technology verification report showing the result of the verification.
Heartbeat Monitoring

Continuously provides device and/or process data for an external system. Analysis of this

data forms the basis for process optimization and predictive maintenance.

7.1.4  

LED module VU120 (optional)

Depending on the MAX/MIN setting, an LED indicates the operational status (switch

status or alarm status) in green, yellow and red. The LED is lit very brightly and is clearly

visible from a large distance.
Connection to the following electronic inserts: FEL62, FEL64, FEL64 DC.

A

 For more details, see the "Electrical connection" section.

8  

Commissioning

8.1  

Function check

Before commissioning the measuring point, check whether the post-mounting and post-

connection checks have been performed:

A

 Checklist in "Post-mounting check" section

A

 Checklist in "Post-connection check" section

8.2  

Functional test using key on electronic insert

• The functional test must be performed in the OK state: MAX safety and sensor free or

MIN safety and sensor covered.

• The LEDs flash one after another as a chaser light during the functional test.

• When performing the proof test in safety instrumented systems according to SIL or

WHG: comply with the instructions in the Safety Manual.

Summary of Contents for Liquiphant FTL64

Page 1: ...Solutions Services Operating Instructions Liquiphant FTL64 Vibronic Point level switch for liquids in high temperature applications BA02037F 00 EN 03 22 00 71560856 2022 02 18 Valid from 01 01 zz Device firmware ...

Page 2: ...Liquiphant FTL64 2 Endress Hauser Order code Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555 ...

Page 3: ...Electrical connection 17 6 1 Required tool 17 6 2 Connecting requirements 17 6 2 1 Cover with securing screw 17 6 2 2 Connecting protective earth PE 17 6 3 Connecting the device 18 6 3 1 2 wire AC electronic insert FEL61 18 6 3 2 3 wire DC PNP electronic insert FEL62 20 6 3 3 Universal current connection with relay output electronic insert FEL64 23 6 3 4 DC connection relay output electronic inser...

Page 4: ...aluminum or 316L 51 13 5 Plug in jack 51 13 6 Bluetooth module VU121 optional 52 13 7 LED module VU120 optional 52 13 8 Sliding sleeves for unpressurized operation 53 13 9 High pressure sliding sleeves 54 14 Technical data 56 14 1 Input 56 14 1 1 Measured variable 56 14 1 2 Measuring range 56 14 2 Output 56 14 2 1 Output and input variants 56 14 2 2 Output signal 57 14 2 3 Ex connection data 57 14...

Page 5: ...ous or fatal injury CAUTION This symbol alerts you to a dangerous situation Failure to avoid this situation can result in minor or medium injury NOTICE This symbol contains information on procedures and other facts which do not result in personal injury 1 2 2 Electrical symbols Ground connection Grounded clamp which is grounded via a grounding system Protective earth PE Ground terminals which must...

Page 6: ... personnel must fulfill the following requirements to carry out the necessary tasks e g commissioning and maintenance Trained qualified specialists must have a relevant qualification for the specific function and task Are authorized by the plant owner operator Are familiar with federal national regulations Must have read and understood the instructions in the manual and supplementary documentation...

Page 7: ...sure continued operational safety and reliability Only perform repair work on the device if this is expressly permitted Observe federal national regulations pertaining to the repair of an electrical device Use original spare parts and accessories from Endress Hauser only Hazardous area To eliminate danger to persons or the facility when the device is used in the hazardous area e g explosion protec...

Page 8: ...wner operator s own security policy must be implemented by plant owners operators themselves 3 Product description Point level switch for minimum or maximum detection Suitable for high temperature applications up to 280 C 536 F 3 1 Product design 1 5 4 2 3 3 A0042420 1 Product design 1 Housing with electronic insert and cover Bluetooth module or LED module are optional 2 Temperature spacer with ga...

Page 9: ... endress com deviceviewer All of the information on the measuring device is displayed along with an overview of the scope of technical documentation provided Enter the serial number on the nameplate into the Endress Hauser Operations app or scan the 2 D matrix code on the nameplate with the Endress Hauser Operations app 4 2 1 Nameplate The information that is required by law and is relevant to the...

Page 10: ...able measures to protect the coating Do not bend shorten or extend the tuning fork A0042422 2 Handling the device during transportation 5 Mounting LWARNING Loss of protection rating if the device is opened in a wet environment Only open the device in a dry environment Mounting instructions Any orientation for device with short pipe up to approx 500 mm 19 7 in Vertical orientation from above for de...

Page 11: ...ted surface of the device Ensure the device is handled properly and professionally during all mounting work 5 1 1 Pay attention to the temperature for devices with a PFA coating conductive The difference in temperature between the outer and inner side of the flange may not exceed 60 C 140 F If necessary use external insulation A B B A C 1 C A0042298 4 Difference in temperature between outer and in...

Page 12: ...ion from the side D Switch point 5 1 3 Take viscosity into consideration Viscosity values Low viscosity 2000 mPa s High viscosity 2000 to 10000 mPa s Low viscosity Low viscosity e g water 2000 mPa s It is permitted to position the tuning fork within the installation socket 25 0 98 50 1 97 A0042333 6 Installation example for low viscosity liquids Unit of measurement mm in High viscosity NOTICE High...

Page 13: ... sockets to ensure that the tuning fork projects freely into the vessel Leave sufficient distance between the buildup expected on the tank wall and the tuning fork A0042345 8 Installation examples for a highly viscous process medium 5 1 5 Take clearance into consideration Allow sufficient space outside the tank for mounting connection and settings involving the electronic insert ...

Page 14: ...ns can damage the coated surface Only use suitable supports Support the device in the event of severe dynamic load Maximum lateral loading capacity of the pipe extensions and sensors 75 Nm 55 lbf ft A0042356 10 Examples of support in the event of dynamic load Marine approval In the case of pipe extensions or sensors longer than 1600 mm a support is needed at least every 1600 mm ...

Page 15: ...nal nut II symbol on the back of the flange 316L G1 A0042348 11 Markings to align the tuning fork Installing in pipes Flow velocity up to 5 m s with a viscosity of 1 mPa s and density of 1 g cm3 SGU Check for correct functioning in the event of other process medium conditions The flow will not be significantly impeded if the tuning fork is correctly aligned and the marking is pointing in the direc...

Page 16: ...e device is delivered 1 Loosen the external locking screw maximum 1 5 turns 2 Turn the housing align the cable entry Avoid moisture in the housing provide a loop to allow moisture to drain off 3 Tighten the external locking screw 5 3 Sliding sleeves A For more details see the Accessories section 5 4 Post mounting check Is the device undamaged visual inspection Does the measuring device meet the me...

Page 17: ...aling Open the cover slacken the screw of the cover lock with a maximum of 2 turns so that the screw does not fall out Fit the cover and check the cover seal Close the cover screw the cover securely onto the housing making sure that the securing screw is positioned correctly There should not be any gap between the cover and housing 2 x 0 7 Nm 4 A0039520 15 Cover with securing screw 6 2 2 Connectin...

Page 18: ...A e g by installing a 1 A fuse slow blow in the phase not the neutral conductor of the supply circuit Power consumption S 2 VA Current consumption Residual current when blocked I 3 8 mA The red LED flashes in the event of an overload or short circuit Check for an overload or short circuit every 5 s The test is deactivated after 60 s Connectable load Load with a minimum holding power rated power of...

Page 19: ...ignaling MAX RD YE GN MIN K K K K K N N N N N IL IL 3 8 mA 3 8 mA 3 8 mA 2 2 2 2 2 1 1 1 1 1 L1 L1 L1 L1 L1 ΔU ΔU A0031901 17 Behavior of switch output and signaling electronic insert FEL61 MAXDIP switch for setting MAX safety mode MIN DIP switch for setting MIN safety mode RD LED red for warning or alarm YE LED yellow switch status GN LED green operational status device on IL Load current switche...

Page 20: ... in conjunction with programmable logic controllers PLC DI modules as per EN 61131 2 Positive signal at switch output of electronics module PNP Functional testing without level change A functional test can be performed on the device using the test button on the electronic insert or using the test magnet can be ordered as an option with the housing closed Supply voltage LWARNING Failure to use the ...

Page 21: ...d current I 350 mA with overload and short circuit protection Capacitance load C 0 5 µF at 55 V C 1 0 µF at 24 V Residual current I 100 µA for blocked transistor Residual voltage U 3 V for switched through transistor Behavior of output signal OK status switched through Demand mode blocked Alarm blocked Terminals Terminals for cable cross section up to 2 5 mm2 14 AWG Use ferrules for the wires Over...

Page 22: ...onnection wiring with M12 plug in housing as per EN61131 2 standard Behavior of switch output and signaling MAX RD YE GN MIN K K K L L L IL 100 µA IL 3 3 3 1 1 1 L L L ΔU ΔU K L 100 µA 3 1 L L 100 µA 3 1 L K A0033508 20 Behavior of switch output and signaling electronic insert FEL62 MAXDIP switch for setting MAX safety mode MIN DIP switch for setting MIN safety mode RD LED red for warning or alarm...

Page 23: ...e and limit the current to 500 mA e g by installing a 0 5 A fuse slow blow in the power supply circuit Power consumption S 25 VA P 1 3 W Connectable load Loads switched via 2 potential free changeover contacts DPDT IAC 6 A Ex de 4 A U AC 253 V P 1500 VA cos φ 1 P 750 VA cos φ 0 7 IDC 6 A Ex de 4 A to DC 30 V I DC 0 2 A to 125 V According to IEC 61010 the following applies Total voltage from relay ...

Page 24: ...ctronic insert FEL64 1 When bridged the relay output works with NPN logic 2 Connectable load Behavior of switch output and signaling 3 5 4 3 5 4 6 8 7 6 8 7 3 5 4 3 3 5 5 4 4 6 8 7 6 6 8 8 7 7 MAX RD YE GN MIN A0033513 22 Behavior of switch output and signaling electronic insert FEL64 MAXDIP switch for setting MAX safety mode MIN DIP switch for setting MIN safety mode RD LED red for alarm YE LED y...

Page 25: ...rcuit Power consumption P 1 0 W Connectable load Loads switched via 2 potential free changeover contacts DPDT IAC 6 A Ex de 4 A U AC 253 V P 1500 VA cos φ 1 P 750 VA cos φ 0 7 IDC 6 A Ex de 4 A to DC 30 V I DC 0 2 A to 125 V According to IEC 61010 the following applies Total voltage from relay outputs and power supply 300 V Preferably use electronic insert FEL62 DC PNP for small DC load currents e...

Page 26: ...DC 1 When bridged the relay output works with NPN logic 2 Connectable load Behavior of switch output and signaling 3 5 4 3 5 4 6 8 7 6 8 7 3 5 4 3 3 5 5 4 4 6 8 7 6 6 8 8 7 7 MAX RD YE GN MIN A0033513 24 Behavior of switch output and signaling electronic insert FEL64 DC MAXDIP switch for setting MAX safety mode MIN DIP switch for setting MIN safety mode RD LED red for alarm YE LED yellow switch st...

Page 27: ...prompted by disconnecting the supply voltage or triggered directly by the Nivotester FTL325P and FTL375P switching unit Supply voltage U 9 5 to 12 5 VDC Reverse polarity protection Comply with the following according to IEC EN61010 1 provide a suitable circuit breaker for the device Power consumption P 150 mW with Nivotester FTL325P or FTL375P Behavior of output signal OK status MAX operating mode...

Page 28: ...with terminals B Connection wiring with M12 plug in housing according to EN61131 2 standard 7 8 Nivotester FTL325P 1 CH FTL325P 3 CH input 1 33 34 Nivotester FTL325P 3 CH input 2 37 38 Nivotester FTL325P 3 CH input 3 d4 d2 Nivotester FTL375P input 1 z4 z2 Nivotester FTL375P input 2 z6 d6 Nivotester FTL375P input 3 Connection cable Maximum cable resistance 25 Ω per core Maximum cable capacitance 10...

Page 29: ...UR IEC 60947 5 6 e g Nivotester FTL325N from Endress Hauser To connect to isolating amplifiers of third party suppliers according to NAMUR IEC 60947 5 6 a permanent power supply for the electronic insert FEL68 must be ensured Signal transmission H L edge 2 2 to 3 8 mA 0 4 to 1 0 mA according to NAMUR IEC 60947 5 6 on two wire cabling Functional testing without level change A functional test can be...

Page 30: ...nals for cable cross section up to 2 5 mm2 14 AWG Use ferrules for the wires Overvoltage protection Overvoltage category II Terminal assignment 0 5 COM MIN MAX 0 7 IEC 60947 5 6 8 2 V DC NAMUR 1 2 L L 1 2 4 3 1 2 1 3 4 M12 L L PE B A A0036066 27 2 wire NAMUR 2 2 mA 1 0 mA electronic insert FEL68 A Connection wiring with terminals B Connection wiring with M12 plug in housing according to EN61131 2 ...

Page 31: ...arm YE Yellow LED switch status GN Green LED operational status device on The Bluetooth module for use in conjunction with the electronic insert FEL68 2 wire NAMUR must be ordered separately with the necessary battery 6 3 7 LED module VU120 optional Supply voltage U 12 to 55 VDC U 19 to 253 VAC 50 Hz 60 Hz Power consumption P 0 7 W S 6 VA Current consumption Imax 0 4 A Connecting the LED module In...

Page 32: ...45108 Operational status signaling MAX RD YE GN MIN RD GN YE A0039258 29 LED module the LED lights up in green GN yellow YE or red RD A brightly lit LED indicates the operational status switch status or alarm status The LED module can be connected to the following electronic inserts FEL62 FEL64 FEL64DC The three colors of the LED flash one after another as a chaser light during the functional test...

Page 33: ...ert FEL68 2 wire NAMUR Service life At ambient temperatures from 10 to 40 C 50 to 104 F the service life of the Bluetooth module without replacing the battery is at least 5 years with a maximum of 60 downloads of complete datasets The battery service life is calculated based on the scenario that the sensor is connected and powered Additional information The battery is categorized as dangerous good...

Page 34: ...tain type of protection the cover is sealed by a securing screw A For more details see the Cover with securing screw section 1 2 3 1 2 A0045097 A0045106 A0045107 4 2 1 A0045108 6 3 9 Connecting the cables Required tools Flat blade screwdriver 0 6 mm x 3 5 mm for terminals Suitable tool with width across flats AF24 25 8 Nm 5 9 lbf ft for M20 cable gland ...

Page 35: ...ainless steel 7 to 12 mm 0 28 to 0 47 in Pay attention to the following when using the M20 coupling Following cable entry Counter tighten the coupling Tighten the union nut of the coupling with 8 Nm 5 9 lbf ft Screw the enclosed coupling into the housing with 3 75 Nm 2 76 lbf ft 6 4 Post connection check Is the device or cable undamaged visual inspection Do the cables used comply with the requirem...

Page 36: ... on the electronic insert MIN 0 7 MAX 0 5 COM U 9 20 V DC 4 3 5 8 7 6 L L 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 A0037705 32 Example of electronic insert FEL64DC 1 COM interface for additional modules LED module Bluetooth module 2 LED red for warning or alarm 3 LED yellow switch status 4 LED green operational status device is on 5 Test button activates functional test 6 DIP switch for setting density 0...

Page 37: ...tes a Heartbeat Technology verification report showing the result of the verification Heartbeat Monitoring Continuously provides device and or process data for an external system Analysis of this data forms the basis for process optimization and predictive maintenance 7 1 4 LED module VU120 optional Depending on the MAX MIN setting an LED indicates the operational status switch status or alarm sta...

Page 38: ...losion protection requirements e g Ex d XP the functional test can also be started from the outside with the test magnet optionally available FEL62 FEL64 FEL64DC FEL68 The functional test of the PFM electronics FEL67 and NAMUR electronics FEL68 can be started at the Nivotester FTL325P N A For more details see the Functional test of the electronic switch with a test magnet section 8 2 1 FEL61 switc...

Page 39: ...il the test button is released The DC PNP output is then switched on again 8 2 3 FEL64 FEL64DC switching behavior and signaling 1 2 1 s 3 MAX MIN YE GN RD YE GN RD 3 4 5 6 7 8 3 4 5 6 7 8 3 4 5 6 7 8 3 4 5 6 7 8 3 4 5 6 7 8 3 4 5 6 7 8 A A0039212 37 FEL64 FEL64DC switching behavior and signaling A After the test button is pressed the relay is de energized for at least 10 s even if the button is pr...

Page 40: ... The output frequency is then 150 Hz again afterwards 1 2 1 s 3 YE GN RD YE GN RD 50 Hz 1 2 L L 150 Hz 1 2 L L 150 Hz 1 2 L L 150 Hz 1 2 L L 150 Hz 1 2 L L A 1 2 L L MIN A0039214 39 FEL67 MIN switching behavior and signaling A After the test button is pressed the output frequency is switched off 150 Hz for at least 10 s even if the button is pressed for 10 s If the test button is pressed for 10 s ...

Page 41: ...ld the test magnet against the marking on the nameplate on the outside Simulation is possible in the case of the FEL62 FEL64 FEL64DC FEL68 electronic inserts The functional test with the test magnet acts in the same way as the functional test using the test button on the electronic insert Ser no Order code Ext ord cd A0033419 41 Functional test with test magnet 8 4 Switching on the device During t...

Page 42: ... the connection for the first time It is important to note the following if the Bluetooth module is removed from one device and installed in another device all log in data are only stored in the Bluetooth module and not in the device This also applies to the password changed by the user 8 5 2 Preparatory steps Note down the ID number of the Bluetooth module The ID number on the nameplate of the Bl...

Page 43: ...5 Tap the icons for more information Change the password after logging in for the first time Saving PDF reports The PDF reports generated in the SmartBlue app are not saved automatically and must therefore be actively saved on the smartphone or tablet ...

Page 44: ...enu Settings and information concerning diagnostics as well as help for troubleshooting Diagnostics Active diagnostics Actual diagnostics Timestamp Diagnostic list Diagnostics 1 Timestamp Diagnostics 2 Timestamp Diagnostics 3 Timestamp Diagnostics 4 Timestamp Diagnostics 5 Timestamp 9 1 2 Application menu Functions for detailed process adaptation to integrate the device optimally into your applica...

Page 45: ...ered to uncovered Output Output state 9 1 3 System menu System settings concerning device management user administration or safety System Electronic type Bluetooth configuration BLE HW revision Information Device tag Serial number Firmware version Device name Order code Manufacturer Manufacturer ID ENP version Operating time Number of system starts ...

Page 46: ...y of the fork increases a corrosion warning appears The order configuration of the oscillation frequency in air is indicated in the verification report An increased oscillation frequency indicates the presence of corrosion A reduced oscillation frequency indicates that there is buildup present or that the sensor is covered by the medium Deviations in the oscillation frequency compared to the oscil...

Page 47: ...ontinuously lit Possible cause Internal sensor error or electronic fault Troubleshooting Replace device No LED is lit only applies for FEL61 Possible cause load current 3 8 mA in the blocked state Troubleshooting replace electronics 10 1 2 SmartBlue Device is not visible in the live list Possible cause No Bluetooth connection available The device is already connected to another smartphone or table...

Page 48: ...EL61 FEL62 FEL64 FEL67 FEL68 Valid from documentation version BA02037F 00 EN 02 20 Changes none 1st version original software 11 Maintenance No special maintenance work is required 11 1 Maintenance tasks 11 1 1 Cleaning It is not permitted to use the device with abrasive media Material abrasion on the tuning fork can result in the device malfunctioning Clean the tuning fork as necessary Cleaning i...

Page 49: ...e listed in the W M Device Viewer www endress com deviceviewer and can be ordered If available users can also download the associated Installation Instructions Device serial number or QR code Located on the device and spare part nameplate 12 3 Return The requirements for safe device return can vary depending on the device type and national legislation 1 Refer to the web page for information http w...

Page 50: ...re parts for the device along with the order code are listed in the Device Viewer www endress com deviceviewer 13 2 Test magnet Order number 71437508 A0039209 43 Test magnet 13 3 Weather protection cover for dual compartment housing aluminum Material stainless steel 316L Order number 71438303 81 3 19 103 4 06 102 5 4 04 73 5 2 89 135 5 31 228 9 9 01 136 4 5 37 65 2 56 92 5 3 64 A0039231 44 Weather...

Page 51: ...t of measurement mm in 13 5 Plug in jack The plug in jacks listed are suitable for use in the temperature range 25 to 70 C 13 to 158 F Plug in jack M12 IP69 Terminated at one end Elbowed 90 5 m 16 ft PVC cable orange Slotted nut 316L 1 4435 Body PVC orange Order number 52024216 27 5 1 08 40 1 57 A0023713 46 Plug in jack M12 IP69 Unit of measurement mm in Plug in jack M12 IP67 Elbowed 90 5 m 16 ft ...

Page 52: ... C o n t a i n s F C C I D I C A0039257 48 Bluetooth module VU121 More detailed information and documentation are available Product Configurator on the Endress Hauser website www endress com Endress Hauser sales organization www addresses endress com A tall cover is required transparent plastic cover or aluminum cover with sight glass when using or retrofitting the Bluetooth module The Bluetooth m...

Page 53: ...e cover depends on the housing and approval of the device 13 8 Sliding sleeves for unpressurized operation Not suitable for devices with PFA conductive coating Not suitable for use in explosive atmospheres Switch point infinitely adjustable 22 0 87 18 0 71 G 1 A 1 NPT G 1 A 1 NPT M6 3x M6 3x 19 0 75 19 0 75 55 3 3 41 A0037666 50 Sliding sleeves for unpressurized operation pe 0 bar 0 psi Unit of me...

Page 54: ...ductive coating Switch point infinitely adjustable Use in explosive atmospheres Seal package made of graphite Graphite seal available as spare part 71078875 For G 1 G 1 seal is included in the delivery G 1 A 1 NPT G 1 A 1 NPT 60 2 36 72 2 83 70 2 76 22 0 87 2 0 08 2 0 08 60 2 36 18 0 71 50 50 5 5 A0037667 51 High pressure sliding sleeves Unit of measurement mm in G 1 DIN ISO 228 I Material 1 4435 ...

Page 55: ...lloyC22 Weight 1 32 kg 2 91 lb Approval with inspection certificate EN 10204 3 1 material NPT 1 ASME B 1 20 1 Material 1 4435 AISI 316L Weight 1 32 kg 2 91 lb Order number 52003669 Order number 52011883 approval with inspection certificate EN 10204 3 1 material NPT 1 ASME B 1 20 1 Material AlloyC22 Weight 1 32 kg 2 91 lb Approval with inspection certificate EN 10204 3 1 material Order number 71118...

Page 56: ... connection relay output FEL64 Switches the loads via 2 floating change over contacts Ambient temperature 60 C 76 F optionally available to order Low temperature electronic inserts are marked LT Direct current connection relay output FEL64DC Switches the load via 2 potential free changeover contacts Ambient temperature 60 C 76 F optionally available to order Low temperature electronic inserts are ...

Page 57: ...ess technology interface Device data and diagnostic data can be read out using the free SmartBlue app 14 2 3 Ex connection data See safety instructions XA All data relating to explosion protection are provided in separate Ex documentation and are available from the Downloads Area of the Endress Hauser website The Ex documentation is supplied as standard with all Ex devices 14 3 Environment 14 3 1 ...

Page 58: ... LED module Relay current 6 A Ta max 65 C 149 F Relay current 4 A Ta max 70 C 158 F With LED module Ta max 10 K 3 Max 50 h on cumulative basis 4 Only for ATEX and CSA certificates Low temperatures are not possible for SIL Bluetooth module 50 C 58 F for non Ex Ex ia and Ex d 60 C 76 F for non Ex LED module 50 C 58 F for non Ex Ex ia and Ex d 60 C 76 F for non Ex Outdoor operation in strong sunlight...

Page 59: ...lies for all housing types Ordering information Select the required option in the order code for Electrical connection Exclusion criteria are taken into account automatically 14 3 7 Vibration resistance As per IEC60068 2 64 2008 a RMS 50 m s2 f 5 to 2000 Hz t 3 axes x 2 h 14 3 8 Shock resistance In accordance with IEC60068 2 27 2008 300 m s 30 gn 18 ms gn standard acceleration of gravity 14 3 9 Me...

Page 60: ...ive 120 K s 14 4 4 Process pressure range LWARNING The maximum pressure for the device depends on the lowest rated element with regard to pressure of the selected component This means that it is necessary to pay attention to the process connection as well as the sensor For pressure specifications see the Mechanical construction section Only operate the device within the specified limits The Pressu...

Page 61: ...ted during the pressure test The mechanical integrity is guaranteed at pressures up to 1 5 times the process nominal pressure PN 14 4 6 Density Liquids with density 0 7 g cm3 Switch position 0 7 g cm3 as delivered state Liquids with density 0 5 g cm3 Switch position 0 5 g cm3 can be set via DIP switch Liquids with density 0 4 g cm3 Optionally available not suitable for SIL applications Fixed value...

Page 62: ...Technical data Liquiphant FTL64 62 Endress Hauser 14 5 Additional technical data Technical Documentation TI01540F ...

Page 63: ...ctronic insert 37 With test magnet 41 I Identifying the device 9 Incoming acceptance 9 Inspection 9 M Mounting Mounting requirements 11 N Nameplate 9 O Operational safety 7 P Post connection check 35 Product safety 7 Purpose of this document 5 R Repair concept 48 Requirements for the personnel 6 Return 49 S Securing screw 17 Spare parts 49 Nameplate 49 T Technical data Environment 57 Transport Han...

Page 64: ...www addresses endress com 71560856 71560856 ...