Operation
Liquiline System CA80PH
116
Hauser
Limit value
Settings
Depends on the measured
value
Operating mode="Above limit check" or "Below limit
check"
a0018080
Abb. 74: Exceeding (A) and falling short of (B) a limit value (without hysteresis and switch-on delay)
1
Limit value
2
Alarm range
t
1
,t
3
,t
5
No action
t
2
,t
4
An event is generated
• If the measured values (MV) are increasing, the relay contact is closed when the on-value ("Limit value" + "Hysteresis")
has been exceeded and the start delay has elapsed ("Start delay").
• If the measured values are decreasing, the relay contact is reset when the off-value is undershot ("Limit value" -
"Hysteresis") and following the release delay ("Switch off delay").
Path: Menu/Setup/Additional functions/Limit switches/Limit switches 1 to 8
Function
Options
Info