Liquiline System CA80AL
Operation
Hauser
99
Menu/Setup/Additional functions/Limit switches/Limit switch 1 ... 8
Function
Options
Info
Delta value
Settings depend on the
measured value
Operating mode
=
Change rate
The slope of the measured value (MV) is
monitored in this mode.
If, in the specified time frame (
Delta time
), the
measured value increases or decreases by more
than the specified value (
Delta value
), an event
is generated. No further event is generated if the
value continues to experience such a steep
increase or decrease. If the slope is back below
the limit value, the alarm status is reset after a
preset time (
Auto Confirm
).
Events are triggered by the following conditions
in the example given:
t
2
- t
1
<
Delta time
and ∆MV1 >
Delta value
t
4
- t
3
>
Auto Confirm
and ∆MV2 <
Delta value
t
6
- t
5
<
Delta time
and ∆MV3 >
Delta value
Delta time
00:00:01 ... 23:59:00
Factory setting
01:00:00
Auto Confirm
00:01 to 23:59
Factory setting
00:01
t
MV
t
1
t
2
t
3
t
4
t
5
t
6
MV
1
MV
2
MV
3
A0028526
77
Rate of change
10.8.2 Controller
Controller structure in Laplace representation
A
B
A0015007
78
Block diagram of the controller structure
A
Neutral zone
I
Integral value
B
Output limiting
D
Derivative value
K
p
Gain (P
‐
value)
αT
V
Damping time constant with α = 0 to 1
T
n
Integral action time (I
‐
value)
e
Control deviation
T
v
Derivative action time (D
‐
value)
w
Set point
T
w
Time constant for set point damping
x
Controlled variable
T
wu
Time constant for anti
‐
windup feedback
y
Manipulated variable
P
Proportional value
The controller structure of the device comprises set point damping at the input to prevent
erratic changes in the manipulated variable if the set point changes. The difference
between the set point w and the controlled variable (measured value) X results in the
control deviation which is filtered by a neutral zone.
The neutral zone is used to suppress control deviations (e) that are too small. The control
deviation thus filtered is now fed to the actual PID controller which divides into 3 parts
based on the P (proportional), I (integral) and D (derivative) values (top-down). The
Summary of Contents for Liquiline System CA80AL
Page 2: ......
Page 117: ...Liquiline System CA80AL Operation Endress Hauser 117 5 Connect the valve or pump ...
Page 175: ......
Page 176: ...www addresses endress com ...