Levelflex M FMP 40 with Foundation Fieldbus
4 Wiring
Hauser
29
4
Wiring
4.1
Quick wiring guide
Wiring in F12 housing
-
-
"
1 2 3 4
EN
DR
ES
S+
HA
US
ER
HA
USER
#
4
5
6
2
3
Made in Germany
D-79689 Maulburg
Dat./Insp.:
Order Code:
IP68 / NEMA 6P
Ser.-No.:
4-wire
HAUSER
t >85°C
TA > 70°C :
D01301-A
if modification
see sep. label
X =
Patents
LEVELFLEX-M
90 … 253 V AC 1VA
10,5 … 32 V DC 1W
16 … 3
V DC 0,8W
Profibus PA
Foundation Fieldbus
LN=
PN=
4 … 20 mA HART
2-wire
1
7
8
3 4
1 2
FF+ FF-
7
Sealed terminal
compartment
Before connection please note the following:
Foundation Fieldbus devices are marked on the nameplate (1).
The voltage is determined by the Foundation Fieldbus
standard and the desired safety concept. (e.g. FISCO).
Connect potential matching line to transmitter
ground terminal
before connecting up the device.
Tighten the locking screw
:
It forms the connection between the antenna and the housing
earth potential.
●
●
●
(7)
(8)
When you use the measuring system in hazardous areas, make sure you comply with
national standards and the specifications in the safety instructions (XA’s).
Make sure you use the specific cable gland.
On devices supplied with a certificate, the explosion protection
is designed as follows:
Housing F12 - EEx ia:
Power supply must be intrinsically safe.
The electronics and the current output are galvanically
separated from the probe circuit.
●
●
Connect up the Levelflex M as follows:
Unscrew housing cover (2).
Remove any display (3) if fitted.
Remove cover plate from terminal compartment (4).
Pull out terminal module slightly using pulling loop.
Insert cable (5) through gland (6).
Use screened, twisted wire pair.
Only ground screen conductor (7) on sensor side.
Make connection (see pin assignment).
Re-insert terminal module.
Tighten cable gland (6).
Tighten screws on cover plate (4).
Insert display if fitted.
Screw on housing cover (2).
(on dust-Ex torque
40 Nm).
●
●
●
●
●
●
●
●
●
●
●
≈
Unplug display connector!
Caution!
plant
ground