Operating menu
Levelflex FMP56, FMP57 FOUNDATION Fieldbus
162
Hauser
Factory setting
0 %
Level (Semiautomatic)
Navigation
Setup → Advanced setup → Linearization → Level
Prerequisite
•
=
Table
•
Table mode (→ 160)
=
Semiautomatic
Description
Displays measured level (value before linearization). This value is transmitted to the table.
Customer value
Navigation
Setup → Advanced setup → Linearization → Customer value
Prerequisite
Linearization type (→ 156)
=
Table
Description
Enter linearized value for the table point.
User entry
Signed floating-point number
Factory setting
0 %
Activate table
Navigation
Setup → Advanced setup → Linearization → Activate table
Prerequisite
Linearization type (→ 156)
=
Table
Description
Activate (enable) or deactivate (disable) the linearization table.
Selection
• Disable
• Enable
Factory setting
Disable
Additional information
Meaning of the options
•
Disable
The measured level is not linearized.
If
Table
at the same time, the device issues error
message F435.
•
Enable
The measured level is linearized according to the table.
When editing the table, the
Activate table
parameter is automatically reset to
Disable
and must be reset to
Enable
after the table has been entered.