Operating menu
Levelflex FMP56, FMP57 FOUNDATION Fieldbus
160
Hauser
Additional information
0%
H
A0013264
H
Intermediate height
The unit is defined in the
Distance unit
Table mode
Navigation
Setup → Advanced setup → Linearization → Table mode
Prerequisite
Linearization type (→ 156)
=
Table
Description
Select editing mode of the linearization table.
Selection
• Manual
• Semiautomatic
• Clear table
• Sort table
Factory setting
Manual
Additional information
Meaning of the options
•
Manual
The level and the associated linearized value are entered manually for each linearization
point.
•
Semiautomatic
The level is measured by the device for each linearization point. The associated
linearized value is entered manually.
•
Clear table
Deletes the existing linearization table.
•
Sort table
Rearranges the linerization points into an ascending order.
*
Visibility depends on order options or device settings