Operating menu
Levelflex FMP56, FMP57 FOUNDATION Fieldbus
146
Hauser
17.3.3 "Advanced setup" submenu
Navigation
Setup → Advanced setup
Locking status
Navigation
Setup → Advanced setup → Locking status
Description
Indicates the write protection with the highest priority that is currently active.
User interface
• Hardware locked
• Temporarily locked
Additional information
Meaning and priorities of the types of write protection
•
Hardware locked (priority 1)
The DIP switch for hardware locking is activated on the main electronics module. This
locks write access to the parameters.
•
SIL locked (priority 2)
The SIL mode is activated. Writing access to the relevant parameters is denied.
•
WHG locked (priority 3)
The WHG mode is activated. Writing access to the relevant parameters is denied.
•
Temporarily locked (priority 4)
Write access to the parameters is temporarily locked on account of internal processes in
progress in the device (e.g. data upload/download, reset etc.). The parameters can be
modified as soon as the processes are complete.
On the display module, the -symbol appears in front of parameters that cannot be
modified since they are write-protected.
Access status tooling
Navigation
Setup → Advanced setup → Access stat.tool
Description
Indicates access authorization to parameters via operating tool (e.g. FieldCare).
User interface
• Operator
• Maintenance
• Service
Additional information
The access authorization can be changed via the
Enter access code
parameter
(→ 147).
If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the
Locking status