Mounting
Levelflex FMP53 PROFIBUS PA
12
Hauser
6
Mounting
6.1
Mounting requirements
6.1.1
Suitable mounting position
A
1
2
C
B
3
A0014130
3
Mounting requirements for Levelflex
Mounting distances
• Distance (A) between wall and rod probe:
– for smooth metallic walls: > 50 mm (2 in)
– for plastic walls: > 300 mm (12 in) to metallic parts outside the vessel
• Distance (B) between rod probe and internal fittings (3) in the vessel: > 300 mm (12 in)
• When using more than one Levelflex:
Minimum distance between the sensor axes: 100 mm (3.94 in)
• Distance (C) from end of probe to bottom of the vessel: > 10 mm (0.4 in).