Operating menu and parameter description
iTHERM TrustSens TM371, TM372
94
Hauser
14.4.1 "System" submenu
Navigation
Setup → Unit
Expert → System → Unit
Damping
Navigation
Expert → System → Damping
Description
Use this function to set the time constant for current output damping.
User entry
0 to 120 s
Factory setting
0 s
Additional information
The current output reacts with an exponential delay to fluctuations in the measured value.
The time constant of this delay is specified by this parameter. If a low time constant is
entered, the current output follows the measured value quickly. On the other hand, if a
high time constant is entered, the current output reaction is delayed.
"Administration" submenu
Define device write protection code
Navigation
Expert → System → Administration → Define device write protection code
Description
Sets a write protection code for the device.
If the code is programmed into the device firmware it is saved in the device and the
operating tool displays the value
0
so that the defined write protection code is not
openly displayed.
User entry
0 to 9
999
Factory setting
0
If the device is delivered with this factory setting the device write protection is not
active.