Wiring
TMT125
38
Hauser
F06-xxxxxxxx-04-xx-xx-xx-005
Fig. 8: Connection hints to retain IP 67 protection
4.5
Post-connection check
After the electrical installation of the device, always perform the following final checks:
Device condition and specifications
Notes
Are the device or the cables damaged?
Visual check
Electrical connection
Notes
Does the supply voltage match the device specification?
9 to 32 V DC
Do the cables used comply with the specifications?
see Operating Instructions on CD-ROM
Do the cables have adequate strain relief?
-
Are the power supply and fieldbus cables correctly connected?
Are all terminals firmly tightened?
-
Are all the cable glands installed, tightened and sealed? Cable run with "water trap"?
33 und
Are all the housing covers installed and tightened?
-
Electrical connection of FOUNDATION Fieldbus™
Notes
Are all the connecting components (T-boxes, junction boxes, connectors, etc.)
connected with each other correctly?
-
Has each fieldbus segment been terminated at both ends with a bus terminator?
-
Has the max. length of the fieldbus cable been observed in accordance with the
FOUNDATION Fieldbus™ specifications?
-
Has the max. length of the spurs been observed in accordance with the FOUNDATION
Fieldbus™ specifications?
-
Is the fieldbus cable fully shielded and correctly grounded?
-