Proline Promag P 500 HART
Commissioning
Hauser
99
Navigation
"Setup" menu → Status input
‣
Status input 1 to n
Assign status input
Terminal number
Active level
Terminal number
Response time status input
Terminal number
Parameter overview with brief description
Parameter
Description
User interface / Selection /
User entry
Factory setting
Terminal number
Shows the terminal numbers used by the
status input module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
• 20-21 (I/O 4)
–
Assign status input
Select function for the status input.
• Off
• Reset totalizer 1
• Reset totalizer 2
• Reset totalizer 3
• Reset all totalizers
• Flow override
Off
Active level
Define input signal level at which the
assigned function is triggered.
• High
• Low
High
Response time status input
Define the minimum amount of time the
input signal level must be present before the
selected function is triggered.
5 to 200 ms
50 ms
*
Visibility depends on order options or device settings
10.4.5 Configuring the current input
The
"Current input" wizard
guides the user systematically through all the parameters that
have to be set for configuring the current input.
Navigation
"Setup" menu → Current input
‣
Current input 1 to n
Terminal number
Signal mode