Proline Promag P 500 HART
Commissioning
Hauser
125
Parameter
Prerequisite
Description
Selection / User
entry / User
interface
Factory setting
ECC cleaning cycle
For the following order code:
"Application package", option
EC
"ECC electrode cleaning"
Enter the pause duration
between electrode cleaning
cycles.
0.5 to 168 h
0.5 h
ECC Polarity
For the following order code:
"Application package", option
EC
"ECC electrode cleaning"
Select the polarity of the
electrode cleaning circuit.
• Positive
• Negative
Depends on the
electrode material:
• Platinum:
Negative
option
• Tantalum, Alloy
C22, stainless
steel:
Positive
option
10.5.6 WLAN configuration
The
WLAN Settings
submenu guides the user systematically through all the parameters
that have to be set for the WLAN configuration.
Navigation
"Setup" menu → Advanced setup → WLAN Settings
‣
WLAN settings
WLAN IP address
Security type
WLAN passphrase
Assign SSID name
SSID name
Apply changes
Parameter overview with brief description
Parameter
Prerequisite
Description
User entry /
Selection
Factory setting
WLAN IP address
–
Enter IP address of the device
WLAN interface.
4 octet: 0 to 255 (in
the particular octet)
192.168.1.212
Network security
–
Select the security type of the
WLAN network.
• Unsecured
• WPA2-PSK
• EAP-PEAP with
MSCHAPv2
• EAP-PEAP
MSCHAPv2 no
server authentic.
• EAP-TLS
WPA2-PSK
Summary of Contents for Hart Proline Promag P 500
Page 210: ...www addresses endress com ...