Commissioning
Gammapilot M FMG60 FOUNDATION Fieldbus
80
Hauser
Options:
•
No
Select this option if no more calibration points are to be entered or changed. The
Gammapilot M then returns to the group selection and the calibration is completed.
•
Yes
Select this option if another calibration point is to be entered or changed. The
Gammapilot M then returns to the
"Calibration point" (*1A)
function and the next
point can be entered or changed.
7.5.4
Linearization (for concentration measurements)
If the concentration is to be measured in a unit other than the
"Density unit" (*06)
, a
linearization must be performed after the basic setup. This is done in the
"Linearization"
(*4)
function group. The individual functions of this group and the linearization procedure
are described in Operating Instructions BA00287F/00/EN, "Gammapilot M - Description of
Device Functions", (on the CD-ROM supplied)
7.5.5
Additional settings
After the basic setup, the Gammapilot M outputs the measured value via the Foundation
Fieldbus interface. Many additional functions are available for optimizing the measuring
point and can be configured as required. For a detailed description of all the device
functions, see BA00287F/00/EN, "Gammapilot M - Description of Device Functions", or the
CD-ROM supplied.
7.6
Density measurement/temperature-compensated
Perform density measurement as described in the "Calibration for density and
concentration measurements" section and then perform temperature calibration (see the
"Temperature compensation" section in BA00287F/00/EN "Gammapilot M - Description of
Device Functions").
7.7
Gammagraphy detection
See the "Gammagraphy" section of BA00287F/00/EN "Gammapilot M - Description of
Device Functions".