Operation
Gammapilot M FMG60 FOUNDATION Fieldbus
50
Hauser
.....ANALOG_INPUT_XXXXXX (AI)
Operation
The Display block contains the parameters for configuring the display module VU331 (in
the remote display and operating unit FHX40). These parameters can also be read out and
edited using the VU 331 display module. The Display block is opened by clicking the
"Display" line. Parameter changes using the tool are made offline. The device can remain in
operation during this time.
The changes are downloaded to the device by first setting MODE_BLK = OOS and then
pressing the WRITE CHANGES button. If you want to check all the values saved in the
device, click READ ALL. To return to operation, set the MODE_BLK to AUTO.
Block administration parameters
Parameter
Description
MODE_BLK
See the description under Resource block. The possible operating modes of the Transducer
block are:
• AUTO: the block is operating as normal
• OOS: the block is out of service
TAG_DESC
User description of the intended application of the block
BLOCK_ERROR Shows the error status in conjunction with the block components
Out-of-Service: the block is in the OOS mode
Device-specific parameters
Parameter
Posi-
tion
indica-
tor
Rel.
index
Variable name
Size[bytes] Type
Read Write Storage
class
Language
*92
13
LANGUAGE
1
ENUM8
X
X
Non-vol.
Back to
home
*93
14
BACKTOHOME
1
INT16
X
X
Non-vol.
No. of deci-
mals
*95
15
NOOFDECIMALS
1
ENUM8
X
X
Non-vol.
Sep. charac-
ter
*96
16
SEPARATIONCHAR-
ACTER
1
ENUM8
X
X
Non-vol.
Unlock
parameter
*A4
17
OPERATIONCODE
2
UNSIGNED16 X
X
Non-vol.
6.6.9
Analog Input block
E+H_GAMMAPILOT_M_XXXXXXXXXXX
.....RESOURCE_XXXXXX (RB2)
.....TRANSDUCER_XXXXXX (TBUL)
.....
ANALOG_INPUT_1_XXXXXX (AI)
The Analog Input block processes the output signal of the Transducer block and forwards it
to the PLC or other function blocks.
4)
If it is not possible to set MODE_BLK to AUTO, an error has occurred. Should this happen, check all the parameters, make the necessary changes
and try to set MODE_BLK to AUTO again