Integration into a FOUNDATION Fieldbus network
Micropilot FMR51, FMR52 FOUNDATION Fieldbus
24
Hauser
6.2.4
Closing the cover of the connection compartment
1.
2.
2,5 Nm
3 mm
A0021491
1. Screw down the cover of the connection compartment.
2. Turn the securing clamp 90 ° in the clockwise direction and, using an Allen key (3 mm),
tighten the screw of the securing clamp on the connection compartment cover with
2.5 Nm.
7
Integration into a FOUNDATION Fieldbus network
7.1
Device description file (DD)
You require the following to configure a device and integrate it into an FF network:
• An FF configuration program
• The Cff file (Common File Format: *.cff)
• The device description (DD) is in one of the following formats:
• Device description format 4 : *sym, *ffo
• Device description format 5 : *sy5, *ff5
Data for device-specific DD
Manufacturer ID
0x452B48
Device type
0x1028
Device revision
0x01
DD Revision
Information and files available at:
•
www.endress.com
•
www.fieldcommgroup.org
CFF Revision
7.2
Integration into the FF network
• For more in-depth information on integrating the device into the FF system, see the
description for the configuration software used.
• When integrating the field devices into the FF system, make sure you are using the
right files. You can read out the required version by means of the Device Revision/
DEV_REV and DD Revision/DD_REV parameters in the Resource Block.