background image

Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus

Basic safety instructions

Hauser

5

To ensure that the measuring device remains in proper condition for the operation time:

Use the measuring device only for media to which the process-wetted materials have an

adequate level of resistance.

Observe the limit values in the "Technical data".

Incorrect use

The manufacturer is not liable for damage caused by improper or non-intended use.
Verification for borderline cases:

For special fluids and fluids for cleaning, Hauser is glad to provide assistance in

verifying the corrosion resistance of fluid-wetted materials, but does not accept any

warranty or liability.

Residual risks

Due to heat transfer from the process as well as power loss in the electronics, the temperature

of the electronics housing and the assemblies contained therein (e.g. display module, main

electronics module and I/O electronics module) may rise up to 80 °C (176 °F). When in

operation, the sensor may reach a temperature close to the medium temperature.
Danger of burns from contact with surfaces!

In the event of high medium temperatures, ensure protection against contact to prevent

burns.

3.3  

Workplace safety

When working on and with the device:

Wear the required personal protective equipment according to federal/national

regulations.

With divisible probe rods, medium may penetrate the joints between the individual parts of

the rod. This medium may escape when the joints are loosened. This can cause injuries in the

case of dangerous (e.g., aggressive or toxic) media.

When loosening the joints between the individual parts of the probe rod, wear appropriate

protective equipment according to the medium.

3.4  

Operational safety

Risk of injury!

Operate the device only if it is in proper technical condition, free from errors and faults.

The operator is responsible for the interference-free operation of the device.

Modifications to the device

Unauthorized modifications to the device are not permitted and can lead to unforeseeable

dangers:

If modifications are nevertheless required, consult with the manufacturer.

Repair

To ensure continued operational safety and reliability:

Carry out repairs on the device only if they are expressly permitted.

Observe federal/national regulations pertaining to the repair of an electrical device.

Summary of Contents for FOUNDATION Fieldbus Levelflex FMP51

Page 1: ...uctions they are not a substitute for the Operating Instructions pertaining to the device Detailed information about the device can be found in the Operating Instructions and the other documentation A...

Page 2: ...e Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555 2 About this document 2 1 Symbols 2 1 1 Safety symbols...

Page 3: ...erminals that must be connected to ground prior to establishing any other connections The ground terminals are located on the inside and outside of the device Inner ground terminal protective earth is...

Page 4: ...the plant owner operator Are familiar with federal national regulations Must have read and understood the instructions in the manual and supplementary documentation Follow instructions and comply with...

Page 5: ...ontact with surfaces In the event of high medium temperatures ensure protection against contact to prevent burns 3 3 Workplace safety When working on and with the device Wear the required personal pro...

Page 6: ...environment the degree of protection indicated on the nameplate is no longer valid This may also impair the safe operation of the device 3 5 1 CE mark The measuring system meets the legal requirement...

Page 7: ...played 4 3 Storage and transport 4 3 1 Storage temperature Permitted storage temperature 40 to 80 C 40 to 176 F Use original packaging Option for FMP51 and FMP54 50 to 80 C 58 to 176 F This range appl...

Page 8: ...Incoming acceptance and product identification Levelflex FMP51 FMP52 FMP54 FOUNDATION Fieldbus 8 Endress Hauser A0013920...

Page 9: ...elflex FMP51 FMP52 FMP54 FOUNDATION Fieldbus Mounting Endress Hauser 9 5 Mounting 5 1 Mounting requirements 5 1 1 Suitable mounting position A C 1 2 3 4 B A0012606 1 Installation conditions for Levelf...

Page 10: ...ernal fittings 3 300 mm 12 in When using more than one Levelflex Minimum distance between the sensor axes 100 mm 3 94 in Distance C from the end of the probe to the bottom of the vessel Rope probe 150...

Page 11: ...ly grounded or reliably insulated Use an insulated fastening kit if it is not otherwise possible to secure the probe with a reliably insulated connection To prevent an extremely high tensile load e g...

Page 12: ...nt mm in 1 Probe rod uncoated 2 Sleeve with narrow bore to ensure electrical contact between the sleeve and the rod 3 Short metal pipe e g welded in place 4 Probe rod coated 5 Plastic sleeve e g PTFE...

Page 13: ...a narrow bore to ensure good electrical contact between the sleeve and the probe rod NOTICE Welding can damage the main electronics module Before welding Ground the probe rod and remove the electroni...

Page 14: ...ad 1 1 2 450 Nm Recommended torque when using the supplied aramid fiber seal and a process pressure of 40 bar only FMP51 no seal is included with FMP54 Thread 3 4 25 Nm Thread 1 1 2 140 Nm When instal...

Page 15: ...ncontrolled swinging of the weight as this could damage internal fittings in the vessel 5 2 4 Turning the transmitter housing To provide easier access to the connection compartment or display module t...

Page 16: ...90 counterclockwise 2 Unscrew the electronics compartment cover and check the cover seal replace it if necessary Turning the display module 1 2 A0036401 1 Pull out the display module with a gentle ro...

Page 17: ...ent 1 2 2 5 Nm 3 mm A0021451 1 Screw down the cover of the electronics compartment 2 Turn the securing clamp 90 in the clockwise direction and using an Allen key 3 mm tighten the screw of the securing...

Page 18: ...ls 3 and 4 without integrated overvoltage protection 3 Connection switch output open collector terminals 3 and 4 with integrated overvoltage protection 4 Connection PROFIBUS PA FOUNDATION Fieldbus ter...

Page 19: ...voltage E 2 wire FOUNDATION Fieldbus switch output G 2 wire PROFIBUS PA switch output Non hazardous Ex nA Ex nA ia Ex ic Ex ic ia Ex d ia XP Ex ta DIP CSA GP 9 to 32 V 3 Ex ia IS Ex ia Ex d ia IS XP...

Page 20: ...evice Connect the potential matching line to the outer ground terminal before applying the power supply Required tools accessories For devices with a cover lock Allen key AF3 Wire stripper When using...

Page 21: ...6 If using shielded cables Connect the cable shield to the ground terminal 6 2 3 Plug in spring force terminals The electrical connection of device versions without an integrated overvoltage protectio...

Page 22: ...ection compartment 2 Turn the securing clamp 90 in the clockwise direction and using an Allen key 3 mm tighten the screw of the securing clamp on the connection compartment cover with 2 5 Nm 7 Operati...

Page 23: ...nd error symbol if an error is active 1 2 Measured value symbols 1 3 Measured value 1 4 Unit 2 Measured value display bar graph 1 value 2 1 Bar graph for measured value 1 2 2 Measured value 1 includin...

Page 24: ...039284 8 Display module 1 Operating keys Key assignment Key Navigate down in the picklist Edit the numerical values or characters within a function Key Navigate up in the picklist Edit the numerical v...

Page 25: ...measurement should generally be completely configured Setup Mapping Mapping of interference echos Setup Advanced setup Contains additional submenus and parameters For more customized configuration of...

Page 26: ...l display appears Calling up the menu via the context menu 1 Open the context menu 2 Press to navigate to the desired menu 3 Press to confirm the selection The selected menu opens 8 Commissioning 8 1...

Page 27: ...X 20 50 Operation Setup Main menu 0104 1 Display language English Espa ol Fran ais Display language English Deutsch 0104 1 Espa ol Fran ais Display language English Deutsch 0104 1 Betrieb Setup Hauptm...

Page 28: ...h R Reference point of measurement D Distance E Empty calibration zero point L Level F Full calibration span 1 Setup Device tag Enter device tag 2 Setup Distance unit Select the length unit 3 Setup Op...

Page 29: ...l Displays the measured level L for verification purposes 10 Setup Distance Displays the distance D between the reference point R and the level L for verification purposes 11 Setup Signal quality Disp...

Page 30: ...2 DK DC 1 1 A0011177 11 Configuration parameters for interface measurement R Reference point of measurement DI Interface distance distance from flange to DK2 E Empty calibration zero point LI Interfac...

Page 31: ...dium 9 Setup Empty calibration Specify the empty distance E distance from the reference point R to the 0 mark 10 Setup Full calibration Specify the full distance F distance from the 0 mark to the 100...

Page 32: ...www addresses endress com 71565976 71565976...

Reviews: