Configuration and online parameterization
FieldPort SWA50
58
Hauser
Configure the device variables on the "Device Variable Mapping" page → 56.
• If FieldCare or another configuration tool communicates with the FieldPort via a
modem, such as FXA 195 for example, the transmission of burst information is
interrupted.
• Some HART field devices are also able to send burst information. In this case, we
recommend activating the burst mode in the FieldPort only. The burst settings of
the FieldPort are not synchronized with the burst settings of the HART field device.
"Burst Mode" page and "Burst Mode 1" to "Burst Mode 5" pages
The "Burst Mode" page provides an overview of which burst modes are configured. You can
define up to 5 different burst mode messages in the "Burst Mode 1" to "Burst Mode 5"
pages.
You can also configure the burst mode in the offline mode. The burst mode takes effect as
soon as the FieldPort joins the network.
Navigation
• Online parameterization > Application Settings > Burst Mode > Burst Mode 1
• Online parameterization > Application Settings > Burst Mode > Burst Mode 2
• Online parameterization > Application Settings > Burst Mode > Burst Mode 3
• Online parameterization > Application Settings > Burst Mode > Burst Mode 4
• Online parameterization > Application Settings > Burst Mode > Burst Mode 5
Burst messages for the FieldPort SWA50 – factory configuration
Burst message
Factory configuration
1
Every 5 minutes, the FieldPort SWA50 transmits the process values of the field device in
accordance with HART command 3.
2
Every 5 minutes, the FieldPort SWA50 transmits the diagnostic data of the field device
in accordance with HART command 48.
3
Not configured
4
Every 5 minutes, the FieldPort SWA50 transmits its own process values in accordance
with HART command 3.
5
Every 5 minutes, the FieldPort SWA50 transmits its own diagnostic data in accordance
with HART command 48.
Configuring the burst mode
1. Open the page for the parameterization of a burst message, e.g.
Burst Mode 1
page.
2. For the
Burst Mode Control Code
parameter, select the
On
option.
The gray input boxes turn white. Entries are possible.
3. For the
Device Index
parameter, select either the FieldPort SWA50 or the connected
HART field device.