Hauser
HART command Type
Memory address
Device variable
Register count
795/796
Write/Read 40162
Timer type
3
40163 - 40164 (4
bytes)
Timer interval
797/798
Write/Read 40165
Output power in dbm
1
804/805
Read/Write 40166
CCA mode
1
808/809
Read/Write 40167
Currently configured time-to-live
1
810/811
Read/Write 40168
Join priority
1
817
Read
40169
Number of bits in new channel map array
3
40170
Current channel map array
40171
Pending channel map array
818
Write
40169
Number of bits in new channel map array
2
40170
Current channel map array
821/822
Write/Read 40174
Network access mode code
1
840
Read
40390 - 4392 (5
bytes)
Unique ID of device
30
40393 (2 bytes)
Number of graphics active
40394 (2 bytes)
Number of frames active
40395 (2 bytes)
Number of links active
40396
Number of neighbors
40397 - 40398
Average communication latency
40399 (2 bytes)
Number of joins
40400 - 40401
Date of most recent join
40402 - 40403
Time of date when the device most recently
join
40404 - 40405
Number of packets generated by this device
40406 - 40407
Number of packets terminated by this
device
40408 - 40409
Number of data-link layer MIC failures
detected
40410 - 40411
Number of network layer (session) MIC
failures detected
40412 - 40413
Number of CRC errors detected
40414 - 40415
Number of nonce counter values not
received by this device
40416 - 40417
Number of nonce counter values not
received from the device