7 Viewing Information (User Mode)
Fieldgate FXA320
77
Hauser
System Log
The system log displays all the activities since the last start, e.g. e-mail delivery, time fetch, alarms,
etc. Up to 25 lines are displayed. The log is deleted when the Fieldgate is switched off. Table 7-5
explains the significance of the parameters.
Table 7-5: System log messages with meaning
System log message
Meaning
changing config page '<page-name>' from <ip-addr>
A configuration page has been changed from the IP address
indicated. Possible <page-name>s:
• loc: Fieldgate Location.
• user: User Setup.
• if: Network Setup.
• hart: HART Setup.
• special: Special.
• info: Information.
changing sensor data '<device-id>' from <ip-addr>
Field device data have been changed from the IP address
indicated.
email delivered to < 1st / 2nd > recipient < service alarm /
limit alarm / measurement >: <subject>
An e-mail was sent to the corresponding receiving group.
hardware-lock closed
The hardware lock has been closed (i.e. the configuration of
the Fieldgate and the connected field devices can now no
longer be remotely altered).
hardware-lock opened
The hardware lock has been opened.
service adapter connected
service adapter aborted
service adapter disconnected
Service adapter has been connected.
Connection via service adapter has been aborted.
Service adapter cable has been disconnected.
time fetched (<protocol>)
• internal time <seconds>s ahead
• internal time <seconds>s behind
Time has been fetched from the Internet. The internal clock
has been adjusted accordingly.
time switching to <time zone>
Automatic adjustment of the time server to a different time
zone. The parameter "Time Offset (related to UTC)" under
"Settings" -> "Network" -> "Time Server Setup" was
automtically adjusted by the time server as a result of a
change in "Timezone Setting (valid for http time service)".
User '<user>' changed password from <ip-addr>
A user has changed his/her password from the IP address
indicated.
SMS send to xxxxxx
Short SMS message has been sent to telephone number xx.
DynDNS OK
Fieldgate could register with at DynDNS with its IP address
and can now be reached by its URL.
< Log> cleared from <ip-addr>
An Administrator has cleared a log at the IP address under
ter "Settings" -> "Special" -> "Clear Log Information".
DHCP stopped
The DHCP Client was stopped since no DHCP server
replied. In this case the IP address set manually under "Set-
tings" -> "Network" -> "IP-Address" is used.
BOOTP failed - using manual entry
The BOOTP Client was stopped, because no server reacted.
In this case the IP address set manually under "Settings" ->
"Network" -> "IP-Address" is used.
received new certificate for FIS communication
Fieldgate has received a certificate for the encrypted com-
munication with the FIS.
FIS registration successful: <http Response Code>
Fieldgate has succesfully registered with the FIS.
received new configuration from FIS
A new Fieldgate configuration was received from the FIS.
FIS message "<subject>" send successfully:
<http Response Code>
Limit or alarm message about <subject> successfully
transmitted to the FIS.
time updated from FIS request
Successful time synchronisation between Fieldgate and FIS.